NBS Source
I'm a manufacturer
Compare variants

VAM-J8 - Heat Recovery Ventilation System

Verified by manufacturer 4 months ago

VAM350J8

Daikin Ltd Variant:

Heat recovery ventilation systems for recovering waste energy from internal spaces to reduce the load on air conditioning and heating systems.

Jump to:
+44 (0)845 641 9000 Website

Application

  • Suitable for most commercial applications with fresh air requirements up to 2000 m³/h.
  • Particularly suitable for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings.

Description

The VAM-J8 series heat recovery ventilation systems are very high-efficiency heat recovery ventilation systems designed to deliver fresh air into occupied spaces whilst reducing the load on the heating and cooling systems by up to 73%. The VAM-J8 series is fully compliant with the 2018 ErP lot 6 legislation and incorporates DC fan motors and a specially developed heat exchange element without the need for any condensate drainage. A full range of optional accessories are available including CO2 sensors to maintain indoor air quality whilst decreasing energy consumption and a range of filters from M6 (medium) to F7 (fine) can be used to allow flexibility of design. Heater batteries are also

available which aid the heat exchange efficiency at low ambient conditions. Weatherproof enclosures can also be purchased for when there is a need to install the VAM units outside. For applications with high humidity or where odours might be present, please see Daikin's Modular Light series which uses aluminium heat exchangers for high-efficiency sensible energy recovery.


Features and benefits:

  • Energy-saving ventilation using indoor heating, cooling and moisture recovery.
  • Free cooling possible when outdoor temperature is below indoor temperature (e.g. during night time).
  • Reduced energy consumption thanks to specially developed DC fan motor.
  • Prevent energy losses from over-ventilation while improving indoor air quality with optional CO2 sensor.
  • Can be used as standalone or integrated in the Sky Air or VRV system.
  • Optional medium and fine dust filters M6, F7, F8 to meet customer request or legislation.
  • Shorter installation time thanks to easy adjustment of nominal air flow rate through the remote controller, so less need for dampers compared with traditional installation.
  • No drain piping needed.
  • Positive and negative pressure settings are available.

General information

Color

Black

Shape

Rectangle

Length

1113 mm

1354 mm

Width

866 mm

920 mm

1172 mm

Height

305 mm

368 mm

731 mm

Uniclass

Pr_60_65_03_87 Supply and return air-handling unitsPrimary

Specification data - Supply and return air-handling units

Duty

-

Air volume

-

Supply

0.056–0.097 m³/s.

Environment

External.

Internal.

Components

-

Filters

Not required.

EKAFVJ50F6 Air filter for VAM350/ 500 J: Medium M6.

EKAFVJ50F7 Air filter for VAM350/ 500 J: Fine F7.

EKAFVJ50F8 Air filter for VAM350/ 500 J: Fine F8.

Heat recovery

-

Heat recovery equipment

Heat exchange element.

Accessories

GSIEKA20024 Inlet Heater Battery.

BRC1H52W Wired touch screen remote controller - White

BRC1H52S Wired touch screen remote controller - Silver

BRC1H52K Wired touch screen remote controller - Black

KRP2A52 and UK.FB2 System adaptor PCB for remote on/off status indication and temperature setting.

RTD-Net and UK.FB2 Modbus Interface PCB for Sky Air and VRV.

RTD-20 and UK.FB2 Energy control PCB for Sky Air and VRV.

KRP50-2 PCB Adaptor for VAM-A series connection to humidifier.

BRP4A50A PCB Adaptor for VAM-B Series connection to 3rd party heater or humidifier.

BRYMA65 CO2 Sensor for VAM350/ 500/ 650.

Power supply

Single phase, 230 V, 50 Hz.

SoundPressure

29–34.5 dBA.

Guidance for specification option:

Heat Exchange Mode.

Sustainability data

Recyclability

70%

Literature

VAM-J8 Data Sheet

VAM-J8 Data Sheet