Verified by manufacturer 4 months ago
HP10
Range of air to water heat pumps for DHW (domestic hot water) that uses CO2 (carbon dioxide - R744) natural refrigerant fluid.
Suitable for applications where a high production of hot water is required, such as:
VIRDIS HP Series for the production of domestic hot water up to 90°C compatible with high temperature difference (ΔT), equipped with heat pump technology providing high energy efficiency using CO2 natural refrigerant in an air-water monobloc configuration for nominal heating capacity from 10 to 100 kW.
Features and benefits:
Color | Grey Other |
Finish | Painted |
Material | Stainless steel |
Shape | Rectangle |
Length | 1100 mm 1650 mm 2400 mm 3050 mm |
Width | 900 mm 970 mm 1120 mm |
Height | 2050 mm 2100 mm 2400 mm |
Uniclass | |
CAWS | T90/505 Air-to-water heat pumps T90/505 Air-to-water heat pumps |
Standards | |
Safety and environmental | To BS EN 378-1 and BS EN 378-2.Guidance for specification option:
|
Test requirements | To EN 14276-1 and EN 14276-2. |
Electrical safety | To To EN 61439-1 and EN 60204-1. |
Heat pump type | Monobloc. |
Mode | Heating. |
Coefficient of performance (minimum) | 3.6.Guidance for specification option:
Manufacturer guidanceWater at 10℃/ 60℃ - Air 7℃ D.B./ 6℃ W.B. |
Output | |
Heating | 9.5 kW.Guidance for specification option:
Manufacturer guidanceWater at 10℃/ 60℃ - Air 7℃ D.B./ 6℃ W.B. |
Fan | |
Type | Axial. |
Fan drive | Direct. |
Configuration | Horizontal. |
Electrical supply type | Three phase. |
Compressor | |
Type | Reciprocating. |
Sealing | Semi-hermetically sealed. |
Drive | Inverter driven. |
Accessories | Not required.Soft starter inverter.Domestic hot water pump.Ducted option.Low noise.Cold Recovery.Coils enhanced corrosion protection. |
Refrigerant | Carbon dioxide.Guidance for specification option: R744. |
Integral accessories | Water pump, Modbus TCP/ IP and remote monitoring. |
Dimensions | 1100 x 900 x 2050 mm. |
Weight | 360 kg. |
Country of product manufacture | United Kingdom |