NBS Source
I'm a manufacturer
Compare variants

Application

  • For heat and smoke ventilation (H&S) and daily comfort ventilation.
  • Can be used in larger and medium-sized buildings e.g. shopping centres, schools or sport/leisure facilities.
  • Can be used in very large buildings by linking several panels together.

Description

Modular smoke ventilation panel for the control of ±24 V d.c. motors and motors with MotorLink® for smoke ventilation and daily comfort ventilation. Comfort ventilation is also possible with KNX or BACnet IP due to bus technology together with e.g. NV Advance®. The linking of panels can be carried out from the beginning or later via CAN. Distance between two smoke control panels up to 250 m with a maximum total distance of 1000 m. Built-in uninterruptible power supply for a minimum of 72 hours in case of power loss (batteries are to be ordered separately).


Features and benefits:

  • Only one type of group (each group can be set as H&S and/ or natural ventilation).
  • Low power consumption.
  • 20 A, 40 A or 60 A as standard per panel, more panels can easily be linked without any additional modules.
  • For both ±24 V standard motors and/or motors with Motorlink®.
  • Easy configuration via the built-in touch screen.
  • Less cabling as the panel uses bus technology.
  • Wind direction depending H&S ventilation is standard, additional modules are not needed.

General information

Color

Grey

Material

Metal

Shape

Rectangle

Length

210 mm

Uniclass

Pr_75_50_18_80 Smoke and heat exhaust control panelsPrimary

Specification data - Smoke and heat exhaust control panels

Enclosure

-

Ingress protection (minimum)

IP54.

Material

Metal.

Colour

Grey (RAL 7035).

Nominal voltage

1 x 230 V a.c.

Nominal frequency

50 Hz.

Outputs

20 A.

Batteries

-

Type

Back-up battery type WSA 017.

Voltage

12 V/17–18 Ah.

Battery autonomy (stored energy time at rated power)

>72 hours.

Guidance for specification option:

In accordance with EN 12101-10.

Mounting

Surface mounting.

Standard

To EN 12101-10.

Modules

WSA 5PS Power supply module 20 A with 1 pcs. end of line module WSA 510.

WSA 5MC NCO Overall control module without field bus interface.

WSA 5MC KNX Overall control module with field bus interface for KNX/BACnet IP.

WSA 5IO Input/output module.

WSA 5SM Motor module for ±24 V standard motors with 4 pcs. end of line module WSA 510.

Show more

Manufacturer guidance

Refer to data sheet for details.

Accessories

None.

WSK 501 000x Break glass unit with signal, primary, plastic housing, with data communication.

Guidance for specification option:

Smoke detectors and keypads can be connected to the break glass unit. Colour of the housing = x: red = 1, yellow = 2, grey = 3, orange = 5.

WSK 502 000x Break glass unit with signal, primary, metal housing, with data communication.

Guidance for specification option:

Smoke detectors and keypads can be connected to the break glass unit. Colour of the housing = x: yellow = 2, grey = 3, orange = 5.

WSK 503 000x Break glass unit with signal, primary, plastic housing, with data communication.

Guidance for specification option:

Smoke detectors and keypads can not be connected to the break glass unit. Requires FlexiSmoke™ firmware version 0.85 or later. Colour of the housing = x: red = 1, yellow = 2, grey = 3, orange = 5.

WSK 504 000x Break glass unit with signal, primary, metal housing, with data communication.

Guidance for specification option:

Smoke detectors and keypads can not be connected to the break glass unit. Requires FlexiSmoke™ firmware version 0.85 or later. Colour of the housing = x: yellow = 2, grey = 3, orange = 5.

Show more

Literature

WSC 520 / 540 / 560 Data Sheet

WSC 520 / 540 / 560 Data Sheet

Similar products from WindowMaster Control Systems Ltd

WSK 200 - ventilation keypad

WSK 200 - ventilation keypad