NBS Source
I'm a manufacturer
Compare variants

Apollo / Apollo ATI natural flap roof ventilators

Verified by manufacturer 5 months ago

Apollo natural flap roof ventilator

Colt International Ltd Variant:
Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Natural smoke extract and day-to-day ventilator with or without weathered ventilation facility.

Jump to:
+44 (0)23 9245 1111 Website

Application

Natural smoke extraction and day-to-day ventilation.

Suitable for most kinds of industrial buildings and is usually installed on building rooftops. May be installed either onto roofs or into barrel vault daylighting systems.

Description

Natural flap ventilators providing both smoke and day-to-day ventilation. It allows extract ventilation for most kinds of industrial buildings and is usually installed on building rooftops. 

Apollo ATI includes weathered ventilation via longitudinal side flaps.


Features and benefits:

  • Wide range of applications: Both models are classed as dual-purpose ventilators, providing day-to-day and smoke control ventilation, and generally installed onto roofs providing high-level extract. Polycarbonate versions allow the entry of natural daylight. Manual, pneumatic or electric controls are available.
  • Efficient and weather-resistant: Aerodynamically efficient. The sealing system consists of EPDM profiles which keep air leakage down to a minimum.
  • Weathered ventilation (Apollo ATI only): Longitudinal flaps and deflectors set within a wind baffle provide aerodynamic ventilation when the weather is wet.
  • Easy to install: Delivered fully assembled to site. Wide range of base profiles to suit most sheeting, curb or glazing applications.
  • Durable: Manufactured from tough, corrosion-resistant aluminium with stainless steel hinges. Tested and certified as fall-through-proof in 300J and 1200J tests by an external test house. Manufactured under the ISO 9001 quality and ISO 14001 environmental management standards.
  • Certified performance: Has been exhaustively tested and certified to EN 12101-2: 2003 in accredited third party test laboratories and is CE marked.
  • High thermal performance: Highly insulated and air tight, meeting or exceeding current energy savings regulations. Good U-value, as low as 1.5 W/m²K.
  • High acoustic performance: With the aluminium lidded version, a sound reduction of up to 28/ 26 dB Rw (Apollo/ Apollo ATI) may be achieved.
  • Manufactured under the ISO 9001 quality standard. Each unit is given a functional test before dispatch.
  • Low in weight.
  • Many colour options (mill finish aluminium as standard).
  • Low price-to-performance ratio.

General information

Color

Silver

Other

Finish

Mill

Material

Steel

Aluminium

Shape

Rectangle

Square

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary

CAWS

L10/47 Roof ventilators

L10/490 Roof ventilators

Product range

Natural flap ventilators

Specification data - Natural smoke and heat exhaust ventilators

Standard

To BS EN 12101-2.

Opening type

B.

Mounting

Roof mounted, onto curb.

Roof mounted, onto glazing.

Onto curtain walling.

Roof mounted, onto roof sheeting.

Aerodynamic free area

Maximum: 7.5 m².

Reliability classification

Re 1000.

Guidance for specification option:

10 000 cycles.

Snow load classification

Manufacturer's standard.

Guidance for specification option:

Up to 5700 N/m² (electric), 1500 N/m² (pneumatic).

Low ambient temperature classification

T (-15).

Wind load classification

WL 1500.

Guidance for specification option:

Aerodynamic coefficient (Cv): Up to 0.68.

Resistance to heat classification

B300.

Arrangement

Flap.

Dimensions

-

Length

-

Manufacturer guidance

Insert requirements, 1000–3000 mm (1 mm increments).

Width

-

Manufacturer guidance

Insert requirements, 1000–2500 mm (1 mm increments).

Height

Manufacturer's standard.

Controls

Pneumatic cylinders.

Guidance for specification option:

Snow load: Up to 1500 N/m².

24 V electric actuators.

Guidance for specification option:

Snow load: Up to 5700 N/m².

Manual.

Initiation

Manufacturer's standard.

Materials

-

Ventilator

-

Frame

Corrosion-resistant aluminium alloy grade 3005 in accordance with EN 573-3.

Guidance for specification option:

With stainless steel fixings.

Louvres

As arrangement.

Glazing

16 mm clear polycarbonate lid.

Guidance for specification option:

Seven skins, six chambers

16 mm opaque polycarbonate lid.

Guidance for specification option:

Seven skins, six chambers

16 mm grey (non-light transmitting) polycarbonate lid.

Guidance for specification option:

Seven skins, six chambers

10 mm clear polycarbonate with 6 mm solid external sheet lid.

Guidance for specification option:

Single chamber.

10 mm opaque polycarbonate with 6 mm solid external sheet lid.

Guidance for specification option:

Single chamber.

20 mm double-skin insulated aluminium infill panel lid.

32 mm clear polycarbonate lid.

Guidance for specification option:

8–10 chambers, U-value of 1.1–1.3 W/m²K.

32 mm opaque polycarbonate lid.

Guidance for specification option:

8–10 chambers, U-value of 1.1–1.3 W/m²K.

Finish

Mill finish.

Polyester powder coated.

Guidance for specification option:

Standard film thickness: 75 µm.

Colour

Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Integral upstands

-

Material

Double-skin aluminium (insulated).

Single-skin aluminium.

Manufacturer guidance

Consult manufacturer for insulation options.

Finish

To match frame.

Mill finish.

Polyester powder coated.

Guidance for specification option:

Standard film thickness: 75 µm.

Colour

To match frame.

Silver.

Guidance for specification option:

Standard for mill finish.

RAL.

Guidance for specification option:

Many colour options available; consult manufacturer for details and insert requirements.

Seals

Manufacturer's standard.

Guidance for specification option:

Rubber; used to reduce air leakage when closed.

Fixing

Onto curb.

Onto glazing.

Onto curtain walling.

Onto roof sheeting.

Locking

Double.

Failsafe closed.

Failsafe open.

U-value

Manufacturer's standard.

Guidance for specification option:

As low as 1.5 W/m²K; consult manufacturer for details.

Resistance to fire

E.

Guidance for specification option:

To EN 13501-1.

Air permeability

Class 3.

Guidance for specification option:

To EN 12207:2000.

Sound insulation

28 dB Rw.

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

Certificate of constancy of performance - Apollo and Apollo ATI

Literature

Apollo natural roof ventilator

Apollo natural roof ventilator