Verified by manufacturer 5 days ago
European Technical Approvals
Certificate type
European Technical Approval (ETA)
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
Fire rated mastic
Suitable for preventing the spread of fire and smoke through joints and openings in fire rated walls and floors (including openings formed around building service penetrations). Suitable for use with most materials, but should not be used in direct contact with bituminous materials.
Designed to prevent the spread of fire and smoke through joints and openings in fire rated walls and floors (including openings formed around building service penetrations); the Astro PFP FR Acrylic will also maintain the acoustic design performance. When subjected to atmospheric conditions, the sealant cures however, it will retain a degree of elasticity for joint movement.
When subjected to atmospheric conditions, the sealant cures however, it will retain a degree of elasticity for joint movement. Under fire exposure, The Astro PFP FR Acrylic creates a robust fire seal by the formation of a durable intumescent char. The Astro PFP FR Acrylic can be used with a suitable filling material i.e. stone wool or Astro PFP FR backing material in order to secure correct width to depth ratio, and to reduce the shrinking of the sealant during curing. Minimum depth and maximum width of the joints are included in the installation instructions.
When testing pipes, one can choose not to cap (or close) the pipe, or cap the pipe inside the furnace, or outside the furnace, or on both sides. The configuration chosen depends on the intended application of the pipe and/or the installation environment. The code defining if a pipe is capped is stated after the fire classification. For instance, EI 60 C/U which means the pipe was capped inside the furnace, and uncapped outside the furnace. The test configuration defines the approvals possible.
Features and benefits:
Color | White |
Finish | Acrylic |
Material | Acrylic |
Shape | Formless |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | P12/47 Sealant P12/390 Sealant |
Third-party certification | UKCA: 0843-UKTA-23/0027 and 23/0028, 0843-CPR-1319. CE: CE-ETA - 21/0030 and 21/0031, CE-2531-CPR-CXO10147. |
Material | Water-based acrylic intumescent. |
Fire performance | |
Fire resistance | Up to EI 240.Manufacturer guidanceExpansion in fire: 1:2–3. |
Reaction to fire | B-S1,d0. |
Durability | Z2 intended for use in internal conditions with humidity |
Flexibility | 12.5% in mortar/concrete/masonry EN ISO 9046. |
ThermalConductivity | 0.845 W/mK (±3%) at 20 mm depth. |
Curing | Totally hardened: 3 to 5 days depending on thickness and temperature. |