NBS Source
I'm a manufacturer
Compare variants

Atlantic LED CG-Line - Self-Contained Safety and Exit Sign

Verified by manufacturer 5 months ago

Atlantic LED S 1-8h/D CGLine+, Single-Sided - 40071354870

Eaton Electric Variant:

Adaptive escape sign luminaire that enables real-time adjustment of exit routes according to the nature and location of a hazard.

Jump to:
01753 608 700 Website

Application

  • Particularly suitable for use in outdoor areas or in industrial applications.
  • Atlantic LED R and Atlantic LED O are suitable for use in food processing industry in accordance with standards IFS and HACCP.
  • Applications include factories, warehouses, underground car parks, workshops, tunnels, escape routes and corridors.

Description

The Atlantic LED CGLine+ luminaire series fulfils protection rating IP65, and with UV-resistant materials and an especially tough construction, it is particularly suitable for use in outdoor areas or in industrial applications. Atlantic LED R and Atlantic LED O are also suitable for use in food processing industry in accordance with standards IFS and HACCP.


The range includes safety luminaires with different optics for escape route or anti-panic illumination and single sided or double sided exit signs. The use of LEDs, automatic testing and monitoring devices (CGLine+) significantly reduce the operating and maintenance costs of the installation.


Features and benefits:

  • 24 m viewing distance.
  • High luminance >500 cd/m².
  • Li-Ion battery.
  • Selectable duration of 1 h, 3 h, 8 h.
  • Comply with the requirements of food-law HACCP.
  • CGLine+ technology.
  • Degree of protection IP65 and IK10.
  • Robust construction from aluminium diecast.
  • High impact resistant cover made of polycarbonate.
  • Wall and ceiling installation.
  • Safety luminaire with asymmetric and symmetric optics.
  • Optional versions with a self-regulating battery heater allow ambient temperature down to -20°C.

General information

Color

Grey

Material

Aluminium

Polycarbonate

Shape

Rectangle

Width

303 mm

Uniclass

Pr_70_70_48_25 Emergency luminairesPrimary
Pr_70_70_48_77 Self-contained emergency luminaires

CAWS

V90/530 Self-contained emergency luminaires

V90/510 General-purpose luminaires

V90/510 General purpose luminaires

Specification data - Emergency luminaires

Standards

To BS EN 60598-2-22.

Luminaire description

Exit sign luminaire Atlantic LED S, single sided, CGLine+.

Classification

-

Electric shock

Class I.

Ingress protection (minimum)

IP65.

Circumstances of use

Normal.

Type

X.

Mode of operation

0.

1.

Duration of emergency mode (minimum)

60.

Guidance for specification option:

Configurable duration, 1 h, 3 h or 8 h.

Impact protection (minimum)

IK10.

Controlgear position

Integral within luminaire.

Nominal voltage

230 V a.c.

Guidance for specification option:

50/60 Hz.

Luminaire power factor

Not applicable.

LED luminaires

-

Initial LED luminaire efficacy (minimum)

Guidance for specification option:

Light source: LED, not exchangeable.

Wattage

7.0 W.

Guidance for specification option:

7.2 VA.

Graphical symbol format

Pictogram, right.

Pictogram, left.

Pictogram, down.

Batteries

Li-Ion battery, 3.7 V/ 4 Ah.

Housing

Aluminium die-cast housing.
White polycarbonate reflector.
Clear polycarbonate diffuser.

Housing colour

Grey.

Mounting

Wall surface mounting.

Ceiling surface mounting.

Literature

Atlantic LED CG-Line

Atlantic LED CG-Line