NBS Source
I'm a manufacturer

Application

  • Specifically designed for use within mechanical shaft ventilation applications.
  • Suitable for installation in vertical ducts or shafts.

Description

The Colt Defender F2 EI60S is a fire rated smoke control damper that controls the movement of smoke through a building. It has been specifically designed to form part of a smoke ventilation system and is ideally suited to the Colt Shaft system, and can be controlled as part of the shaft system network.


Features and benefits:

  • Distinctive design creates a flush finish with the wall when closed, making it extremely discreet when installed.
  • External surfaces can be painted to match surrounding walls.
  • Constructed from mild steel and fire rated A1 non-combustible calcium silicate board.
  • Mineral wool insulation.
  • Advanced, multi-stage sealing system ensures smoke leakage is controlled in both ambient and fire conditions.
  • Fire rated to provide 60 minutes of integrity and insulation when closed.
  • Motor release from the corridor/lobby side for ease of maintenance.
  • Smoke sealed.
  • Suitable for applications covered by ADB/9999/9991/ SCA Guide.
  • Tested to EN 1363-1 and BS EN 1366 Parts 2 and 10.
  • Certified to EN 12101 Part 8 and is classified to EN 13501-4 (EI60 (Ved i<>o) S 1000 C300 AA Multi).
  • CE and UKCA marked.

General information

Color

White

Guidance for specification option:

RAL 9010 as standard.

Other

Guidance for specification option:

Other colours are available on request.

Finish

Satin

Matt

Gloss

Material

Steel

Guidance for specification option:

Mild steel.

Calcium silicate

Guidance for specification option:

Fire rated A1 non-combustible calcium silicate board.

Mineral wool

Guidance for specification option:

Insulation.

Shape

Rectangle

Length

1325 mm

Width

740 mm

Uniclass

Pr_65_65_24_80 Smoke dampersPrimary

CAWS

U90/445 Dampers, smoke

U90/445 Dampers, smoke

Specification data - Smoke dampers

Standard

To BS EN 12101-8.

Classification

-

Standard

To BS EN 13501-4.

Multi-compartment

-

Integrity class

EI 60.

Guidance for specification option:

Integrity, insulation and smoke sealing: 61 minutes.

Suitability

Ve duct.

Smoke leakage

S.

Under pressures

1000.

Inside or outside

(i ↔ o).

Smoke control use

C300.

Activation

AA – automatic.

Actuators

Tested to BS EN 1366-10.

Verification

-

Submittals

Manufacturer's data sheet.

Aperture size

564 x 1151 mm.

Dimensions

740 x 1325 mm.

Guidance for specification option:

Includes perforated bead edge to allow plaster finish right up to aperture edge.

Manufacturer guidance

Overall dimensions.

Colour

White.

Guidance for specification option:

Standard.

Other.

Guidance for specification option:

Other colours are available on request. Consult manufacturer for details and insert requirements.

Surface finish

Matt.

Satin.

Gloss.

Literature

Colt Defender F2 Smoke Control Damper Data Sheet

Colt Defender F2 Smoke Control Damper Data Sheet