Verified by manufacturer 6 months ago
Fire rated smoke control damper.
The Colt Defender F2 EI60S is a fire rated smoke control damper that controls the movement of smoke through a building. It has been specifically designed to form part of a smoke ventilation system and is ideally suited to the Colt Shaft system, and can be controlled as part of the shaft system network.
Features and benefits:
Color | White Guidance for specification option: RAL 9010 as standard. Other Guidance for specification option: Other colours are available on request. |
Finish | Satin Matt Gloss |
Material | Steel Guidance for specification option: Mild steel. Calcium silicate Guidance for specification option: Fire rated A1 non-combustible calcium silicate board. Mineral wool Guidance for specification option: Insulation. |
Shape | Rectangle |
Length | 1325 mm |
Width | 740 mm |
Uniclass | |
CAWS | U90/445 Dampers, smoke U90/445 Dampers, smoke |
Standard | To BS EN 12101-8. |
Classification | |
Standard | To BS EN 13501-4. |
Multi-compartment | |
Integrity class | EI 60.Guidance for specification option: Integrity, insulation and smoke sealing: 61 minutes. |
Suitability | Ve duct. |
Smoke leakage | S. |
Under pressures | 1000. |
Inside or outside | (i ↔ o). |
Smoke control use | C300. |
Activation | AA – automatic. |
Actuators | Tested to BS EN 1366-10. |
Verification | |
Submittals | Manufacturer's data sheet. |
Aperture size | 564 x 1151 mm. |
Dimensions | 740 x 1325 mm. Guidance for specification option: Includes perforated bead edge to allow plaster finish right up to aperture edge. Manufacturer guidanceOverall dimensions. |
Colour | White. Guidance for specification option: Standard. Other. Guidance for specification option: Other colours are available on request. Consult manufacturer for details and insert requirements. |
Surface finish | Matt. Satin. Gloss. |