NBS Source
I'm a manufacturer
Compare variants

CR60-1S - "ZERO liabilities" - EIS Circular Fire Damper (max Ø 315mm) - Fire Damper

Verified by manufacturer 22 hours ago

CR60-1S fire damper

Rf-Technologies Variant:
Third party certifications:
  • Classification report acc. to EN 13501-3

    Certificate type

  • DoP

    DoP

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications. (previously known as FD and FSD / MFSD)

Jump to:
+44 7939316006 Website

Application

CR60-1S - Innovative, "near-ZERO" liabilities - Circular Fire Damper - EIS - 60–90 minutes (max Ø 315mm)


Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.

(previously known as FD and FSD / MFSD)


CR60-1S Certified installations and sealing methods:

  • In wall & floor:
  • rigid wall & floor.
  • flexible wall.
  • asymmetrical flexible wall (shaft wall).
  • Remote of wall.
  • For full details: CR60 Declaration of Performance (DoP) - see associated content.


CR60-1S Fields of application:

  • Passive fire protection.
  • Ventilation systems.


CR60-1S Building applications:

  • Industrial, commercial & residential buildings.
  • Hospitals and care houses.
  • Data centres and battery plants.
  • Detention institutes.
  • Universities, colleges and schools.

Description

CR60-1S - Innovative, "near-ZERO" liabilities - Circular Fire Damper - EIS - 60–90 minutes (max Ø 315mm)


Circular EIS fire damper, requiring NO SEALING and consequently bringing "near-ZERO" CE/UKCA liabilities and improved installation flows, with a fire resistance of 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.

(previously known as FD and FSD / MFSD)


CR60-1S Distinct Product Features (incl. specifications)

  • Integrated CE/UKCA fire sealing !
  • CE certified against EN 1366-2 and EN 15650.
  • UKCA certified.
  • i <-> o certified.
  • Air-tightness class C against EN 1751.
  • Up to 500 Pa pressure level (standard 300 Pa).
  • Minimal distance certified against EN-1366-2.
  • Single, thin insulated damper blade.
  • No mechanics inside the damper body.
  • Fusible link aligned with the open damper blade.
  • 72°C fusible link temperature threshold.
  • Insulated damper body (to meet I criteria).
  • Support lugs aligned to DW145 guidance.
  • Designed for use with Belimo motor range (24/ 230 V).
  • Designed for use with ONE motor range (24/ 230 V).
  • Designed for use with ONE-X and ZENiX.
  • Note for clarification:
  • ONE is a motor by Rf-Technologies.
  • ONE-X is motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.


CR60-1S User Benefits:

  • Minimal impact on building space requirements thanks to the minimal distance CE certification and the compact damper and mechanics design
  • down to 30 mm vs. structure or between dampers (instead of 200 mm standard CE).
  • Minimal pressure loss in the damper body and ventilation system
  • ultimately leading to lower system investments and energy consumption.
  • Minimal acoustic / noise impact.
  • Lowest standby power consumption in the market when using the ONE motor.
  • Easy installation and maintenance (compared to traditional UK type fire dampers).


CR60-1S range:

  • Diameter (mm) 100 to 315.
  • Tunnel casing (mm) 345 or 500.


Notes:

  • For information about the different types of installation and sealing methods please consult the CR60 Product application field and or the CR60 Declaration of Performance (DoP).
  • CR60-1S info is included in the CR60 documentation
  • For a 120 minutes requirement please consult the CR120-1S.


Relevant Links:

General information

Color

White

Silver

Finish

Galvanized

Guidance for specification option:

Standard body (casing) (steel)

Epoxy

Guidance for specification option:

Inner body & blade

  • Optional at order
  • Resistance against "aggressive" fluids and gases

Material

Steel

Guidance for specification option:

Casing.

Shape

Circle

Length

345 mm

Guidance for specification option:

Standard models.

500 mm

Guidance for specification option:

L500 models.

Width

100 mm

125 mm

160 mm

200 mm

250 mm

Show more

Manufacturer guidance

Diameter.

Height

100 mm

125 mm

160 mm

200 mm

250 mm

Show more

Manufacturer guidance

Diameter.

Warranty description

One year

Third party certifications

Classification report acc. to EN 13501-3

Classification report acc. to EN 13501-3

CR60 Classification Report

DoP

DoP

CR60 Declaration of Performance (DoP)

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

CR60 UKCA Certificate

Literature

CR60 Technical Product Documentation

CR60 Technical Product Documentation

Case studies

CR60 and ONE Reference Project - Resecentrum Göteborg, Sweden

CR60 and ONE Reference Project - Resecentrum Göteborg, Sweden