Verified by manufacturer 14 days ago
CU-LT fire damper
Classification report acc. to EN 13501-3
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
DoP
Certificate type
Hygiene requirements to VDI 6022
Certificate type
Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications. (previously known as FD or FSD / MFSD)
Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications.
(previously known as FD or FSD / MFSD)
CU-LT Certified installations and sealing methods
CU-LT Fields of application
CU-LT Building applications
Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications.
(previously known as FD or FSD / MFSD)
CU-LT Distinct Product Features (incl. specifications)
CU-LT user benefits:
CU-LT range:
CU-LT configurations & options:
Notes:
Color | Silver White |
Finish | Galvanized Guidance for specification option: Casing (steel). Epoxy |
Material | Steel Guidance for specification option: Casing. |
Shape | Rectangle Square |
Length | 300 mm Guidance for specification option: Casing depth, standard CU-LT model. 500 mm Guidance for specification option: Casing depth, CU-LT-L500 model. |
Width | 200 mm 250 mm 300 mm 350 mm 400 mm |
Height | 100 mm 150 mm 200 mm 250 mm 300 mm |
Warranty description | One year |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Standard | |
Fire dampers | To EN 15650:2010. |
Test | To EN 1366-2. |
Classification | To EN 13501-3. |
Arrangement | Single-blade. |
Classification | Guidance for specification option: To EN 13501-3, up to EI 120 (ve ho i <-> o) S - (500 Pa) depending on installation method; consult manufacturer and insert details. |
Material | Galvanized steel.Guidance for specification option: Tunnel casing. Consult manufacturer for details of other components. |
Accessories | IFW CU-LT pre-mounted installation kit for flexible wall.UL inspection shutter.Guidance for specification option: Set of two. PRJ circular connection.Guidance for specification option: Circular connection flange with rubber sealing ring. Note: This supersedes the PG20 connection. Limit switch (open/closed).Guidance for specification option: Available for fusible links only (see Thermal release mechanism). Additional limit switch (open/closed).Guidance for specification option: Second limit switch, available for actuators only (see Thermal release mechanism). None. |
Fusible links | |
Fusing temperature | 72°C. |
Dimensions | Guidance for specification option: Consult manufacturer's literature for performance details including pressure loss, and insert requirements:
Standard unit weight between 3.2 and 19.2 kg; consult manufacturer's literature for details. Intermediate dimensions available on request. |
Pressure loss | Guidance for specification option: Insert details, dependent on required damper size and air flow/air speed; consult manufacturer's technical literature for details. |
Air tightness | Class C. |
Thermal release mechanism | Actuator - ONE T 24 V. Guidance for specification option: Single limit switch included as standard; See Accessories if an additional switch is required. Actuator - ONE T 230 V. Guidance for specification option: Single limit switch included as standard; See Accessories if an additional switch is required. Actuator - ONE-X 24 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - ONE-X 230 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - Belimo 24 V. Guidance for specification option: Single limit switch included as standard; See Accessories if an additional switch is required. |
Integral accessories | PG20 connection to ducts with 20 mm flanges. Guidance for specification option: PG20 connection:
Inspection opening(s):
|
Third-party certification | CE marked BCCA-0749-CPR-BC1-606-0464-15650.05-0464. |
Country of material origin | Europe |
Country of product manufacture | Belgium |
Classification report acc. to EN 13501-3
CU-LT Classification Report Warringtonfire
UK Conformity Assessed (UKCA)
CU-LT UKCA Certificate
DoP
CU-LT Declaration of Performance
Classification report acc. to EN 13501-3
CU-LT Classification Report Efectis
Hygiene requirements to VDI 6022
CU-LT Hygiene Certificate
CR120 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper
CR2 - Circular EIS Fire Damper (max Ø 630mm) - Fire Damper
CR60 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper
CR60-1S - "ZERO liabilities" - EIS Circular Fire Damper (max Ø 315mm) - Fire Damper
CU2 - Rectangular EIS Fire Damper (max W1500 x H1000 mm) - Fire Damper
CU2/B - Large Rectangular EIS Fire Damper - Maximum Four Individual Fire Dampers
CU4 - Rectangular EIS 4Hours Fire Damper - Fire Damper