Verified by manufacturer 2 months ago
EBLA09DV3
Air-to-water monobloc system.
Suitable for external applications where indoor space is limited.
An outdoor single unit low temperature air-to-water heat pump with the option of heating only or reversible systems.
Features and benefits:
For full technical information, refer to manufacturer's literature.
EBLA(09/11/14/16)D3W1 and EBLA(09/11/14/16)D3V3:
EDLA(09/11/14/16)D3W1 and EDLA(09/11/14/16)D3V3:
Color | Silver Black |
Finish | Coated Guidance for specification option: Polyester painted. |
Material | Steel Guidance for specification option: Galvanized steel plate. Stainless steel Guidance for specification option: Water filter. |
Shape | Rectangle |
Length | 460 mm |
Width | 1380 mm |
Height | 870 mm |
Warranty description | Five year |
Uniclass | |
CAWS | T90/505 Air-to-water heat pumps T90/505 Air-to-water heat pumps |
Standards | |
Test requirements | To BS EN 14511. |
Heat pump type | Monobloc. |
Mode | Heating and cooling. |
Coefficient of performance (minimum) | 4.91 (condition 1); 3.71 (condition 2).Guidance for specification option:
|
Output | |
Heating | 9.37 kW (condition 1); 9.00 kW (condition 2).Guidance for specification option:
|
Cooling | 9.35 kW (cooling 3); 9.10 kW (cooling 4).Guidance for specification option:
|
Fan | |
Type | Propeller.Guidance for specification option: Fan mortar - 230 W output. |
Fan drive | Direct. |
Configuration | Horizontal. |
Electrical supply type | Single phase.Guidance for specification option:
|
Compressor | |
Type | Swing. |
Sealing | Hermetically sealed. |
Drive | Inverter driven. |
Accessories | Back up heater kit.Not required. |
Refrigerant | R32.Guidance for specification option:
|
Dimensions | 870 x 1380 x 460 mm. Manufacturer guidanceUnit height x width x depth. |
Unit weight | 147 kg. |
Sound | To EN14825, 62.0 dB(A). Manufacturer guidanceSound power level. |
Safety devices | High pressure switch, low pressure switch, fan driver overload protector, fuse, and compressor motor thermal protector. |
PipeConnection | G 1" (male). |
Air flow | 2880 m³/h. Manufacturer guidanceRated airflow (outdoor). |
HeatingWaterFlowRate | 26.9 L/min (condition 1); 25.8 L/min (condition 2). Guidance for specification option:
Manufacturer guidanceWater side heat exchanger water flow rate. |
CoolingWaterFlowRate | 26.8 L/min (cooling 3); 26.1 L/min (cooling 4). Guidance for specification option:
Manufacturer guidanceWater side heat exchanger water flow rate. |
Motor | 400 rpm (heating); 500 rpm (cooling). Manufacturer guidanceFan motor speed. |
Material | Polyester painted galvanized steel plate. Manufacturer guidanceCasing material. |
Casing colour | Silver. |
Country of material origin | Europe |
Country of product manufacture | Europe |
Daikin Altherma High Capacity H HT Heat Pump EPRA-DW1/V3 (Sizes 14-16-18) - Heating system
Daikin Altherma Low Capacity H HT Heat Pump EPRA-DW1/V3 (Sizes 8-10-12) - Heating system
Daikin Altherma Low Capacity R32 Monobloc EB/DLA-EV3 (Sizes 4-6-8) - Heat pump
Low Temperature High Capacity R-Split Heat Pump (Size 11-14-16) - Water heater
Low Temperature Low Capacity R-Split Heat Pump (Size 4-6-8) - Heating system