Protecta Plus vertical split load 8 + 4, TPN

ABB Ltd Variant:

Sub-distribution solution from ABB, tailored to meet the needs of all segments of the building industry.

Jump to:
+44 (0)24 7636 8500 Website

Application

Sub-distribution solution suitable for all applications and environments.

Description

Available in kit form for over-the-counter supply, the latest generation sub-distribution solution from ABB has been tailored to meet the needs of all segments of the building industry.


Features and benefits:

  • Structure in epoxy-coated metal sheets, 1 mm thickness.
  • Wall installation for indoor environments.
  • Degree of protection: IP43 with door/ mechanical resistance IK07.
  • Main isolator rating: 125, 160 or 250 A.
  • Number of ways: 8+4, 8+8, 12+8, 12+12, 16+8, 8+4+4 or 12+8+4.
  • Supplied with main isolator and meters, pre-configured to internal current transformer sizing.
  • Outgoing devices to be ordered separately.
  • Three pole as standard; four pole option available.
  • Maximum ambient temperature: +35°C.
  • Compliance with BS EN IEC 61439-1 and BS EN IEC 61439-2.
  • Simple wiring of all cabinets, both horizontally and vertically.
  • Easy internal accessibility for wiring operations and maintenance.
  • Pre-packaged kits for specific applications (e.g. surge protection).

General information

Color

Grey

Guidance for specification option:

RAL 7035.

Finish

Textured

Epoxy

Material

Metal

Shape

Rectangle

Length

125 mm

Manufacturer guidance

Depth.

Width

450 mm

Height

1090 mm

1270 mm

1380 mm

1440 mm

1580 mm

Show more

Warranty description

One year

Uniclass

Pr_60_70_22_22 Distribution boardsPrimary

CAWS

V90/320 Distribution boards

Specification data - Distribution boards

Standards

To BS EN IEC 61439-1 and BS EN 61439-2.

Rated operational voltage (Ue)

415 V a.c.

Incoming device

Manufacturer's standard.

Outgoing devices

-

Type

Guidance for specification option:

To be ordered separately.

Consult manufacturer for options and insert details.

Manufacturer guidance

Available to specify separately.

Quantity

8 + 4.

Busbars and connections

-

Type

Manufacturer's standard.

Guidance for specification option:

Consult manufacturer for details.

Rated current (InA)

125 A.

Guidance for specification option:

Standard cable capacity: 50 mm².

160 A.

Guidance for specification option:

Standard cable capacity: 70 mm².

250 A.

Guidance for specification option:

Standard cable capacity: 95 mm².

Manufacturer guidance

Consult manufacturer for details if larger cables are required.

Rated short-time withstand current (Icw)

Manufacturer's standard.

Guidance for specification option:

Consult manufacturer for details.

Rated conditional short-circuit current (Icc): 35 kA.

Neutral and earth bars

Two brass bars each size (7*10) mm.

Spare ways

As circuit schedules.

Fit with blank plates.

Guidance for specification option:

See Accessories for related options.

Enclosure

-

Ingress protection (minimum)

With door: IP43.
Pan assembly: IP20.

Guidance for specification option:

With door.

Mechanical resistance: IK07.

Material

Cold-rolled sheet steel, 1 mm-thick.

Finish

Electrostatic powder-coating, textured finish.

Colour

RAL 7035 Light Grey.

Locking mechanism

Door closing latch.

Guidance for specification option:

Standard.

Lock and key.

Accessories

None.

Guidance for specification option:

Consult manufacturer for options and insert requirements, or omit.

Surge protection.

Guidance for specification option:

Consult manufacturer for options and insert requirements.

Other.

Guidance for specification option:

Consult manufacturer for all options and insert requirements.

Accessories include:

  • MCB blank.
  • Blanking strip 12 mods.
  • Inner isolator terminal shroud.
  • Top mount TPN DB earth bar.
  • Side-by-side connection kit.
  • MCB padlock adaptor.
  • MCB padlock C/W 2 x keys.
  • DB/ trunking adaptor.
  • Protecta Plus – Glandplate, plain.
  • Protecta Plus door hinge x 1.
  • Protecta Plus screw kit for DB ( 6x M4 x 16 mm, 2x M4 x 30 mm).

Dimensions

1090 x 450 x 125 mm.

Guidance for specification option:

Height x width x depth.

Distance between fixing centres: 1000 x 358 mm.

Integral accessories

Isolator
Two meters.
Associated current transformers.
Incoming terminals.
Internal cables.

Guidance for specification option:

Meters are MID, Modbus (RS485) and pulse output.

Poles

Three.

Guidance for specification option:

Standard.

Four.

Rated insulation voltage

690 V.

Rated frequency

50/ 60 Hz.

Door

Opening angle: 180°.

Other features

Position of knockouts: top and bottom.

Sustainability data

Material

Metal

Literature

Power Distribution Solutions  - Commercial Buildings

Power Distribution Solutions - Commercial Buildings

Similar products from ABB Ltd

Distribution Board Type A – Protecta Plus SPN - MCB Distribution Board

Distribution Board Type A – Protecta Plus SPN - MCB Distribution Board

Distribution Board Type B Split Load Horizontal – Protecta Plus Dual Metered DBs - MCB Distribution Board

Distribution Board Type B Split Load Horizontal – Protecta Plus Dual Metered DBs - MCB Distribution Board

Distribution Board Type B – Protecta Plus - TPN - MCB Distribution Board

Distribution Board Type B – Protecta Plus - TPN - MCB Distribution Board

Panel Board MCCB – Protecta Power - Distribution Board

Panel Board MCCB – Protecta Power - Distribution Board