Two Hour Fire and Radiant Heat Resisting Curtain.

Jump to:
+44 (0)1204 871001 Website

Application

Any internal application where fire compartmentation is required but is ideally suited for : -

Retail Malls, Offices, Receptions / Foyers, Lift Lobbies / Lift Doors, Open-plan Private Residencies.

 

Performance Characteristics:

Resistance to Fire:      E30, E60 or E120 classifications

- Including Rigid and Flexible Structures

Radiated Heat:            EW30

Reduction of 15kW/m² to EW30 classification

 

Fire: Tested to EN1634-1 all in accordance with EN13501- 2, EN15269.

 

Key Attributes:

Fire rated and radiant heat reducing curtain.

CE Marked.

Compact and light weight design.

Bespoke manufacture to suit individual openings.

Range of controls.

 

Description

Bolton Gate Company, the acknowledged leader in the field of rolling fire door technology, are pleased to offer the Fibreroll range of fire rated curtains.

 

These fire curtains are specifically designed to provide fire compartmentation and a protected means of escape all within a compact, aesthetically pleasing yet robust and reliable system.

 

Utilising a fully tested woven glass fabric with stainless steel wire reinforcement, the Fibreroll E120 Rolling Fire Curtain provides not only up to two-hour fire integrity between fire compartments but also  a reduction in radiated heat to such a large extent that it meets the requirements for a rating of EW30.


Operation

Electric operation is by means of a tubular motor suitable for connection to a 230-volt nominal single-phase supply with gravity failsafe closure in a fire condition.

 

A control panel is provided with the facility for connection of a normally closed volt free contact from the Client's fire alarm system . A battery is included to prevent unwanted closing of the curtain in case of power failure.

 

The curtain will automatically descend upon receipt of the fire signal and retract once removed.

 

If the curtain system is to be used on an escape route, only local heat detection can be used. This can be accommodated by our operating controls. 

 

Curtain

Specially reinforced and coated fibreglass material which is designed to withstand temperatures more than 1000 degrees C.

 

Bottom Rail

A steel bottom rail is attached to provide rigidity and act as a weight to assist closure.

 

Side Guides

Manufactured from galvanised steel and formed into a  slimline profile which is prepared for bolting to the opening structure.

 

Roller

The roller comprises a suitable diameter steel tube in which the tubular motor is fitted at one end and steel shafts / discs at the other.


Endplates

Galvanised steel endplates are provided with integrated angles to simplify installation.

 

Coil Casing

The roller is covered by a galvanized steel casing which also acts as a fire seal at the head.

 

Finish

The curtain is supplied in a neutral grey colour with the side guides, bottom rail, and coil casing all supplied in a standard galvanised finish.

 

Maximum Size

5000mm wide x 8000mm high (single roller)

Unlimited width x 6000mm high (multiple rollers)

 

Weight

Curtain 0.78Kg / m² approx.

Barrel / Casing 30Kg / m approx.

 

 Options

- Sounder beacon during closing.

- Voice warning during closing.

- Emergency retract via UPS and push button on 1 or 2 sides

- Two stage or delayed descent.

- Obstruction warning using light curtain or photocell with delayed timer and sounder.

- Side guides, bottom rail and coil casing supplied with  polyester powder coated finish to alternative RAL colour from standard range.

- Local heat detector.

 

General information

Color

Grey

Finish

Galvanized

Powder-coated

Textured

Manufacturer guidance

Side guides, bottom rail and coil casing supplied with  polyester powder coated finish to alternative RAL colour from standard range.

Material

Steel

Shape

Square

Rectangle

Length

Bespoke

Width

Bespoke

Guidance for specification option:

Bespoke sizes.

Single roller - maximum 5000mm wide

Multiple rollers - maximum width is unlimited

Height

Bespoke

Guidance for specification option:

Bespoke sizes.

Single roller - maximum 8000mm high

Multiple rollers - maximum 6000mm high

Warranty description

One year

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Product range

Fire

Specification data - Vertical active fire curtain barriers

Standards

Tested to EN 1634-1 and EN 1634-3 all in accordance
with EN 13501-2, EN 15269-11. These active fire curtains are CE marked all in keeping with BS EN 13241 and EN 16034.

Test standards

Vertical, horizontal and angled to BS EN 1634-1 and -3.

Size

5000 x 8000 mm.

Manufacturer guidance

Insert requirement.

Performance

-

Pressure and impact

Manufacturer's standard.

Durability class

Manufacturer's standard.

Smoke containment

Smoke tight seal.

Fire resistance

E30.

E60.

E120.

Guidance for specification option:

Available up to 16254 x 6740 mm (clear width x clear height).

EW30.

Deployment

Two stage.

Delayed descent.

Activation

In a fire condition, activation is initiated by a normally closed volt free contact from the fire alarm system or, where on a fire exit route, local heat detector. Closure is by gravity with a controlled descent.

Accessories

None.

Emergency retract.

Local heat detector.

Obstruction warning (via light curtain).

Sounder beacon.

Two-stage descent.

Voice warning.

Execution

Installing active fire curtain barrier assemblies.

Colour

Galvanised Steelwork

PPC Option Available

Fixing

Face-fixed.

Soffit-fixed.

Suspended (to a maximum of 500 mm).

Weight

Curtain: 0.78 kg/m², Barrel/casing: 30 kg/m² (approx).

Guidance for specification option:

Approximately.

Radiation

Reduction of 15kW/m² to EW30 classification.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Steel

Manufacturing plant location

Recyclability

50%

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Expected Life

Ten year

Third party certifications

Constructionline Gold

Constructionline Gold

Constructionline Gold

ISO 9001 Quality Management

ISO 9001 Quality Management

Certificate of Management System Registration - ISO 9001:2015

dhf certificate

dhf certificate

DHF Membership

Literature

Fire Curtain - Fibreroll E120 - EW30

Fire Curtain - Fibreroll E120 - EW30