Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel

Verified by manufacturer 26 days ago

Coopers Fire Ltd

Fire Curtain assembly with vision panels that have been tested to the requirements of BS EN 1634-1:2014 and UL 10D

Jump to:
+44 (0)23 9245 4405 Website

Application

Fire Curtain is suitable for use as:

  • Escape routes incorporating doorways and corridors.
  • Lift lobby muster points, lift openings and lobbies.
  • Areas where fire marshals and the fire and rescue service may need to assess prior to entry.


Suitable to be used to form a virtually continuous barrier as a fire separating element.

Description

Fire Curtain - An electrically operated active fire curtain barrier assembly. The barrier assemblies comprises a woven steel and glass fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick stainless steel box. Within the main curtain assembly there are two vision panels. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.


The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (120 minutes integrity). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (30 minutes).


Operation:

Barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the barrier assembly will deploy on receipt of a signal. At the end of the period, the barrier assembly will deploy.


Fire resistance:

120 minutes' (two hours) integrity.


Period of radiation:

Greater than 30 minutes (for a radiation level measured below 15 kW/m²).


Classification:

E120 EW30 C1.


Product certification, performance and/ or testing:

  • Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete barrier assemblies have been tested for fire resistance to BS EN 1634-1. The barrier assembly achieved 120 minutes integrity and 30 minutes radiation.


Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2014 + A1:2018, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1363-1:1999, Fire resistance tests – Part 1: General requirements.
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures.
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating.
  • BS EN 14600:2005, Doorsets and openable windows with fire resisting and/ or smoke control characteristics.
  • BS EN ISO 1716, Determination of the Heat of Combustion for Building Products.
  • BS 6853 Annex B.2, Toxicity.
  • BS 6853 Annex D.8.4, Methods for Measuring Smoke Density.
  • BS EN 13823, Reaction to Fire Tests – Single Burning Item.
  • BS EN 14184-1, Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method.
  • HSG 248, Analysis of Material for the presence of Asbestos.
  • BS EN ISO 9001:2015, Quality management system.
  • BS EN ISO 14001:2015, Environmental management system.


Features and benefits:

  • See through a deployed curtain as a means of escape.
  • Safely egress from lifts.
  • First responder can clear a building faster.
  • First responder can see the presence of an occupant on the other side of a curtain.
  • First responder can see the presence of fire on the other side of a curtain.
  • First responder can see the presence of smoke on the other side of a curtain.

General information

Color

Other

Finish

Galvanized

Material

Steel

Guidance for specification option:

Woven steel.

Fabric

Guidance for specification option:

Glass fabric.

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

BS EN 1634-1, , BS EN 1363-1, BS EN 1363-2, BS EN 13501-2 +A1, BS EN 14600, BS EN ISO 1716, BS 6853, BS EN 13823, BS EN 14184-1, BS EN ISO 9001,BS EN ISO 14001.

Barrier assemblies

To BS EN 1634-1 and BS EN 1634-3.

Test standards

To BS EN 1634-1, BS EN 1634-3 and UL 10D.

Third-party certification

Warringtonfire Certification - Certifire.

Size

Bespoke.

Guidance for specification option:

Insert requirement.

Performance

-

Durability class

C1.

Smoke containment

None.

Fire resistance

120 minutes' (two hours) integrity.

Barrier units

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m² -5%, + 10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item).
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).
  • The fabric type used for the vision panels is ResQ-Window, which is a transparent material, manufactured from a High Silica base fabric with a diluted Silicone coating.

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Beam protection and obstruction warning.

Guidance for specification option:

Beam obstruction detector with delay timer.

Emergency retract.

Guidance for specification option:

Touch button retract facility.

Split drop delay.

Guidance for specification option:

Partially deploys to pre-determined level to permit escape and initial smoke containment.

Visual alert system.

Guidance for specification option:

Light warning system when mains or emergency power is available.

Voice warning.

Guidance for specification option:

Audio or spoken multi-message facility when mains or emergency power is available.

Arrangement

Folded.

Vertical.

Classification

E120 EW30 C1.

Frame colour/ finish

Galvanized steel.

Polyester powder-coated, RAL 9017.

Polyester powder-coated, RAL 9010.

Polyester powder-coated, RAL colour.

Guidance for specification option:

Insert requirement.

Materials

Woven steel and glass fabric.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

285 kg CO₂ eq/kg

Self declared

Manufacturer guidance

285.92 tCO2e for yearly emissions

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Literature

ResQ-WINDOW-UL

ResQ-WINDOW-UL

ResQ-WINDOW

ResQ-WINDOW

Case studies

THE TROCADERO HOTEL, LONDON

THE TROCADERO HOTEL, LONDON

Similar products from Coopers Fire Ltd

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina

Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain