Fire Door Intumescent Acrylic Sealant

Verified by manufacturer 6 months ago

Fire & Acoustic Seals Ltd Third party certifications:
  • IFCC

    IFCC

    Certificate type

  • Certifire Certificate

    Certifire Certificate

    Certificate type

Intumescent Acrylic Sealant can provide up to 120 minutes fire resistance integrity within installations of timber fire door assemblies depending on application and backing material required.

Jump to:
+44 (0) 121 521 2179 Website

Application

Suitable for sealing joints in and around internal partitions and for sealing between fire doors and fire-rated walls.

Description

This intumescent fire and smoke-stopping sealant swells when exposed to temperatures in excess of 125℃.


This product has been specifically tested with fire door assemblies to meet BS 476: Pt 20 & 22: 1987 and is Certifire approved to guarantee its performance. 


Features and benefits:

  • Prevents the passage of fire and smoke.
  • Has a fire rating of up to four hours in certain joint configurations.
  • Certifire Approved (CF5840).
  • Forms a fire and smoke seal in joints up to 35 mm wide without slumping.
  • Available in foil packs or recyclable cartridges.

General information

Color

Brown

White

Grey

Orange

Finish

Acrylic

Material

Sealant

Guidance for specification option:

Intumescent.

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

Product can be stored for at least 18 months from its production date when stored in a cool dry environment, in original unopened container, and at temperatures between +2C and +30C. Do not allow to freeze.

Manufacturer guidance

Product storage - 18 months

Uniclass

Pr_30_31_76_40 Intumescent firestop sealantsPrimary

CAWS

P12/47 Sealant

P12/390 Sealant

Specification data - Intumescent firestop sealants

Third-party certification

Certifire Approved CF5840.

Material

Intumescent acrylic.

Fire performance

-

Fire resistance

To BS EN 1366-3: 2004 and BS EN 1366-4: 2006, 120 minutes.

Guidance for specification option:

For wall installations 130 mm (minimum) thick with FD120 doorsets.

Standard

BS 476-20: 1987, BS 476-22: 1987, BS EN ISO 140-3, EN 13141-1.

Colour

Brown.

White.

Grey.

Orange.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Sealant

Guidance for specification option:

Intumescent.

Recyclability

95%

Guidance for specification option:

Packaging and canister.

Third party certifications

IFCC

IFCC

Fire Door Foam & Intumescent Acrylic Sealant - Kiwa Field of Application Report Par/18385/01 Rev C

Certifire Certificate

Certifire Certificate

Intumescent Acrylic Sealant - No CF 5840

Literature

FAS Fire Door Intumescent Acrylic Sealant Installation Guide

FAS Fire Door Intumescent Acrylic Sealant Installation Guide

Fire Door Intumescent Acrylic Sealant Datasheet

Fire Door Intumescent Acrylic Sealant Datasheet

Case studies

Bespoke Joinery Manufacturer uses Fire Door Foam and Intumescent Sealant on Crawley Town Hall

Bespoke Joinery Manufacturer uses Fire Door Foam and Intumescent Sealant on Crawley Town Hall