NBS Source
I'm a manufacturer

Floodline Ranger® HLD Control Panel - Hybrid Leak Detection Panel

Verified by manufacturer 16 days ago

Andel Ltd

Hybrid leak detection panel with multiple distance measuring and zonal options.

Jump to:
+44 (0)1484 845000 Website

Application

Floodline® Ranger HLD is designed for medium-size installations up to 24 zones or 16 distance measuring cables – or a combination of both.

Description

Floodline Ranger® HLD Control Panel is designed for medium size installations. The panel is a true hybrid that is able to accept input alarms from all Floodline sensors as well as third-party sensors. It allows the sensitivity of each zone to be adjusted to suit the environment and working conditions for that zone, significantly reducing the risk of false alarms.


Features and benefits:

  • Easy-to-use, push button control panel with integrated LCD screen.
  • Full hybrid simultaneous monitoring of zonal and distance measuring leak detection sensors.
  • Monitors full range of Floodline water, oil, gas, temperature and humidity sensors as well as third-party sensors.
  • Can be configured for 6, 12, 18, 24 zones or 4, 8, 12, 16 distance measuring cables (or a combination).
  • A Floodline zone can also be a distance measuring cable.
  • Adjustable zone sensitivity.

General information

Color

Grey

Finish

Powder-coated

Material

Steel

Shape

Rectangle

Length

115 mm

Manufacturer guidance

Depth.

Width

335 mm

Height

350 mm

Warranty description

Ten year

Uniclass

Pr_75_50_18_48 Liquid presence detection programmable control unitsPrimary

Specification data - Liquid presence detection programmable control units

Nominal voltage

230 V a.c.

Guidance for specification option:

Mains operated.

Nominal frequency

50 Hz.

Guidance for specification option:

Mains operated.

Number of zones

6, 12, 18 or 24 zones.
4, 8, 12 or 18 distance measuring.

Controls

-

Display type

LCD screen and status LEDs.

Display the following information

Leak detection and system fault.

Guidance for specification option:

  • Leak detection: continuous water, oil, gas leak detection plus temperature and humidity monitoring with each zone reporting separately.
  • System fault: sensor or cable damage, failure or disconnection.

Features

Fully programmable leak detection monitoring.

Battery backup capacity

12 V d.c. internal and battery backup.

Communications

-

Outputs

Complete power failure (SPCP, 240 V.a.c., 5 Amp).
Mains failure (SPC0, 240 V.a.c., 5 Amp).
System failure (SPCO, 240 V.a.c., 5 Amp).
Zone fault (open/ short circuit) (SPCO, 240 V.a.c., 5 Amp).
Leak detected (SPCO, 240 V.a.c., 5 Amp).

Network protocols

Modbus TCP/ IP.
Modbus RTU.
GSM extension.

Enclosure

-

Material and finish

Fine textured steel, powder-coated, traffic grey (RAL 7043).

Mounting method

Suitable for walls.

Configuration

4 configurable main relays.
6 configurable individual relays (NO/NC).

Dimensions

350 x 335 x 115 mm.

Manufacturer guidance

Height x width x depth.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Literature

Floodline Ranger® HLD Control Panel

Floodline Ranger® HLD Control Panel