Verified by manufacturer 16 days ago
Leak detection system for water or oil leak sensor cables.
Suitable for data centres, plant rooms, warehouses, libraries, museums and any longer areas that require liquid leak detection.
A distance measuring system comprising control panel and detection cable, which provides continuous liquid leak detection for up to 1500 metres.
Can operate as a stand-alone system or can be easily integrated into a larger Floodline® installation (functioning as a zone and connecting to any of the Floodline® control panels). The system provides more choice for projects which require a distance measuring system with the advantage of also working within a network of multiple zones and a range of other sensors in any size of installation.
In the event of a leak detection, the control panel triggers an audio-visual alarm as well as triggering onward communication to building management system (BMS) or similar. Illuminated LEDs on the control panel provide visual indication for power, leak detection, system status alerts and communications. The leak detection LED indicator on the control panel shows the distance to the leak.
Features and benefits:
Color | Grey |
Finish | Powder-coated |
Material | Steel Polymer |
Shape | Rectangle |
Length | 65 mm Guidance for specification option: Detection cable is available in a range of pre-terminated lengths with locking connectors to join the lengths together. |
Width | 181 mm |
Height | 150 mm |
Warranty description | Ten year |
Uniclass |
Sensor types | Water-sensing and oil-sensing cables. |
Control panel | Liquid presence detection programmable control units.Guidance for specification option: Includes controls for mute button and automatic reset. Powder coated, fine textured steel enclosure, RAL 7043. |
Connection cable to sensors | |
Cable type | Conductive polymer cables.Guidance for specification option:
Insert cable length requirement, up to 1500 m. |
Containment accessories | Screw terminals. |
Alarm indication | Audio-visual, with LEDs for cable fault, leak, and four-digit LED display for leak distance in metres. |
System accessories | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Nominal voltage | 230 V a.c. Guidance for specification option: Relay contacts: 125 V a.c., 0.5 A, 24 V d.c., 1 A normally open (can be normally closed). |
NominalFrequency | 50 Hz. Guidance for specification option: Mains operated, 60 W. |
Network type | RS485 communication mode. Guidance for specification option: BAUD rate can be selected, optional address for 0 to 247. Default BAUD rate is 9600 and address is 0. MODBUS RTU. |
Operating temperature | 20–50°C. Guidance for specification option:
|
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |