Verified by manufacturer 5 months ago
Double
Quelfire Intumescent & Acoustic Putty Pads are designed to maintain the fire resistance of plasterboard partitions where they have been penetrated by plastic or metal electric socket boxes.
Quelfire Intumescent & Acoustic Putty Pads are designed to maintain the fire resistance of plasterboard partitions where they have been penetrated by plastic or metal electric socket boxes.
They also make a significant contribution to the reduction of air leakage in properties, helping reduce energy costs and carbon emissions.
Intumescent acoustic putty pads designed to maintain the fire resistance of plasterboard partitions, where they have been penetrated by plastic or metal electric socket boxes.
Composition
Quelfire Intumescent & Acoustic Putty Pads are manufactured from a mouldable, red, non-setting silicone based intumescent polymer.
Fire Performance
When subjected to fire, the Quelfire Intumescent Acoustic Putty Pad reacts forming a robust fi re resistant char to prevent the passage of fi re through the socket box and cable penetrations. They can be installed into sockets that are both offset or back-to-back, plastic or metal, single double or media size and in either single skin or double skin fire rated plasterboard walls as well as in conjunction with BeadMaster socket surrounds. The Quelfire Intumescent Putty Pad has been tested to the principles of BS EN1366-3 up to 120 minutes integrity and insulation. Please refer to specific installation details for specific fire ratings.
Acoustic Performance
The Quelfire Intumescent Acoustic Putty Pad will help with reducing the room-to-room noise transfer through socket penetrations and have been acoustic tested to BS EN ISO 140-3:1995 achieving up to 70dB reduction in standard socket configurations.
Features and benefits:
Standards and approvals:
Installation:
Quelfire Intumescent Acoustic Putty Pads are suitable for use in both metal and plastic electric socket boxes and to suit both single and double electric socket boxes.
They can be fitted during installation of the socket boxes or as a retrofit solution. Installation is simple and requires no special tools or skills and a installation guide is available.
The simple process is: Remove the cover plate, ensure the box is dust free, remove the backing paper and mould the putty pad into the socket box ensuring the socket box is completely covered right out to the front face of the wall, trimming off any excess if required. A slit can be cut with a knife where any wires penetrate and the putty can then be resealed around the wire once fitted.
They can be installed into sockets that are both offset or back-to-back, plastic or metal, single double or media size and in either single skin or double skin fire rated plasterboard walls as well as in conjunction with BeadMaster socket surrounds. For step by step installation guide for these scenarios, please refer to the associated "Installation Instructions" document.
Color | Red |
Material | Intumescent Guidance for specification option: Intumescent putty pads. Polymer |
Shape | Other Guidance for specification option: Cross. |
Width | 170 mm 70 mm 230 mm |
Height | 170 mm 70 mm 230 mm |
Uniclass | |
CAWS | P12/350 Intumescent putty |
Material | Non-setting, silicone based Intumescent acoustic putty pads. |
Form | Preformed pads.Guidance for specification option:
|
Socket box type | Double electrical socket boxes. Guidance for specification option: Suitable for plastic and metal electric socket boxes and switch boxes. |
AcousticRating | Up to 70 dB reduction. Guidance for specification option: Acoustic tested to BS EN ISO 140-3: 1995. |
FireRating | ≤2 h. Guidance for specification option: Tested to the principles of BS EN 1366-3: 2009 and assessed to BS EN 1363-1: 2012. |
Country of product manufacture | United Kingdom |