High performance ULTIMATE™ wired mat for fire protection of circular ductwork.
HVAC - Fire Protection of Ductwork
U Protect Wired Mat 4.0 Alu1 is a lightweight and easy to install ULTIMATE™ mineral wool wired mat. It combines all the advantages of conventional thermal and acoustic insulation with excellent fire performance and is a component of the U Protect System.
The U Protect system has been tested in accordance to EN 1366-1 and EN 1366-8 and assessed against the criteria in BS 476: Part 24. It offers up to 2 hours passive fire protection in HVAC ventilation and smoke extract ducts as well as up to 1 hour passive fire protection for kitchen ducts.
The fire resistance is also dependent on the application, thicknesses of insulation and the method of installation.
Please contact technicalsupport@saint-gobain.com for further details.
Product Features:
Fire Classification:
Euroclass A1 Reaction to Fire classification according to EN 13501-1.
Product Benefits:
1 Fire resistance is dependent on the application, thicknesses used and method of installation.
The system includes a range of accessories (intumescent paint, glue, screws and tape) to ensure the correct installation of the U Protect system. For further details, please visit insulation-uk.com/hvac-insulation/ductinsulation-fire-protection or contact technicalsupport@ saint-gobain.com.
Key Considerations:
When using Isover U Protect Wired Mat 4.0 Alu1, you need to satisfy yourself that use of the product meets all relevant national Building Regulations and guidance as well as local, national and other applicable standards relevant for your construction or application, including requirements in relation to fire.
Please refer to the following product documents:
Color | Black Yellow |
Finish | Aluminium |
Material | Mineral wool Guidance for specification option:
|
Uniclass | |
CAWS | U90/490 Site-applied insulation to ductwork U90/490 Site-applied insulation to ductwork |
Standard | To EN 14303. |
Thermal conductivity | 0.031-0.096 W/m.K (10–400°C).Guidance for specification option:
|
Finish | Aluminium foil faced. |
Reaction to fire classification | Euroclass A1 Reaction to Fire classification according to EN 13501-1. |
Insulation thickness (minimum) | 30 mm.50 mm.60 mm.75 mm.80 mm.90 mm.100 mm.120 mm. |
Vapour barrier | |
Material | Aluminium. |
Accessories | Manufacturer's standard.Guidance for specification option: A full range of accessories is available to help ensure effective fire protection and straightforward installation. |
Execution | Installing mineral wool insulation on ducts. |
Product Reference | ISOVER U PROTECT Wired Mat 4.0 Alu1 |