NBS Source
I'm a manufacturer
Compare variants

PAROC Hvac Mat AluCoat - Stone Wool Mat with Reinforced Facing

Verified by manufacturer 19 days ago

100 mm thick

Paroc Ltd Variant:
Third party certifications:
  • DoP

    DoP

    Certificate type

Stone wool mat with reinforced aluminium foil facing.

Jump to:
BOS
+447974699156 Website

Application

Suitable for thermal and condensation insulation of circular and rectangular ventilation ducts.

Description

Thermal and condensation insulation of air ducts and other ventilation ducts and equipment.


Features and benefits:

  • Plastic packaged.
  • CE marked.


The surface temperature of the facing must not exceed +80°C (temperature restriction determined in accordance with the heat resistance of adhesive).

PAROC stone wool products are capable of withstanding high temperatures. The binder starts to evaporate when its temperature exceeds approximately 200°C. The insulating properties remain unchanged, but the compressive stress weakens. The softening temperature of stone wool products is over 1000°C.

General information

Color

Silver

Finish

Foil

Material

Stone wool

Shape

Rectangle

Length

4000 mm

5000 mm

7000 mm

8000 mm

Width

500 mm

1000 mm

Uniclass

Pr_80_77_76_53 Mineral wool duct slab insulationPrimary

CAWS

J31/26 Thermal insulation

H92/775 Thermal insulation

Specification data - Mineral wool duct slab insulation

Form

Mat.

Thermal conductivity

0.046 W/m·K at 50°C.

Guidance for specification option:

  • 0°C: 0.034 W/m·K.
  • 10°C: 0.036 W/m·K.
  • 50°C: 0.046 W/m·K.
  • 100°C: 0.060 W/m·K.
  • 150°C: 0.075 W/m·K.
  • 200°C: 0.093 W/m·K.
  • 250°C: 0.115 W/m·K.

Finish

Reinforced aluminium foil facing.

Fire performance

To EN 13501-1, Euroclass A1.

Insulation thickness (minimum)

100 mm.

Manufacturer guidance

To EN 823:

Combustibility

To EN ISO 1182:2002, Class 0 according to BS 476: Part 6 1989 and Part 7 1997.

Length

4000 mm.

Manufacturer guidance

To EN 822:

Water absorption

≤1 kg/m².

Thickness tolerance

T2.

Water vapour diffusion resistance

To EN 14303:2009+A1:2013 (EN 12086), MV2.

Dimensional stability

To EN 14303:2009+A1:2013 (EN 14706), (+/100) 250°C.

Width (nominal)

500 mm.

1000 mm.

Manufacturer guidance

To EN 822.

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

DoP

DoP

PAROC Hvac Mat AluCoat - DoP

Literature

PAROC Hvac Mat AluCoat - datasheet

PAROC Hvac Mat AluCoat - datasheet