QB50 QuelStop Fire Batt is an ablative coated mineral wool board used to reinstate the fire rating of wall and floor constructions where they have been penetrated by services.
QB50 QuelStop Fire Batt is an ablative coated mineral wool board used to reinstate the fire rating of wall and floor constructions where they have been penetrated by services.
Features and benefits:
Standards and approvals:
Size
1200mm x 600mm, 50mm thick, 140kg/m³ density.
Packaging & Storage
QuelStop Fire Batt is supplied as a 1200x600mmx50mm slab, individually wrapped in polythene and is usually shipped on a pallet and must be stored in dry conditions between +5 and +40C.
Health & Safety
QuelStop Fire Batt is manufactured from stone wool insulation which consists of small fibres. Appropriate protective clothing, including gloves, dust mask, safety glasses, should be worn, especially during cutting and installation, to guard against dust inhalation, eye and skin irritation. For further information, please refer to the Material Safety Data Sheet, available on request.
Installation:
QuelStop Fire Batt is used to maintain the fire integrity of compartment walls or floors, typically where oversized holes have been formed for services. A single or double batt may be required depending on a number of factors and it can also be fitted as a pattress fit (or face fit) too.
QuelStop Fire Batt is always installed in conjunction with QuelStop Intumescent Acrylic Sealant which is applied to all cuts, joints and exposed edges.
Where combustible, non-combustible services and insulated services penetrate the QuelStop Fire Batt seal the following additional products may be required:
For full details on the size of seals, the spacing of services, batt overlap requirements, seal details etc refer to all available documentation.
QuelStop Fire Batt can be installed in many different ways. In all cases the surfaces, letterbox and services must be clean of contaminants and dust free and the batt must be installed with QuelStop Intumescent Acrylic Sealant and in conjunction with the supporting documentation provided.
Color | Orange Guidance for specification option: Fire Batt. White Guidance for specification option: Ablative Coating. |
Material | Mineral wool Guidance for specification option: Ablative coated mineral wool fire batt. |
Shape | Rectangle |
Length | 50 mm |
Width | 1200 mm |
Height | 600 mm |
Uniclass | |
CAWS | P12/360 Mineral wool rigid batts P12/40 Mineral wool rigid batts P12/41 Mineral wool rigid batts - ablative coated |
Fire rating | Class A1, ≤2 h fire rating (EI 30, EI 90, EI 120).Guidance for specification option:
|
Thickness | 50 mm. |
Edges | Square. |
Finish | Ablative coated. |
Colour | Fire Batt: Orange, Ablative Coating: White. |
Dimensions | 1200 x 600 x 50 mm. Guidance for specification option: Fire Batt/ Slab. Manufacturer guidanceL x W x T. |
Form | Solid. |
Odour | Fire Batt: Odourless, Ablative Coating: Barely perceptible. |
PHLevel | 5–9. |
Density | Fire Batt: 140 kg/m³, Ablative Coating: 1.45–1.55 relative density. |
Sound insulation rating | 60 dB. Guidance for specification option: Acoustic tested to EN 10140. |
Country of product manufacture | United Kingdom |
Material | Mineral wool Guidance for specification option: Ablative coated mineral wool fire batt. |