S-Line® Pillows

Verified by manufacturer 2 days ago

S100FP – S-Line® Sausage

FSi Limited Variant:
Product certifications:
  • UL-EU Certified

    UL-EU Certified

    Certificate type

Fire resistant penetration sealing system.

Jump to:
+44 (0)1530 515130 Website

Application

Application / Use:

  • To reinstate fire resistance through rigid walls and floors.
  • Multi-service penetrations.
  • Prevention of air leakage.
  • Maintains Acoustic performance.
  • Fire Stopping within steel cable trunking · For internal use.

Description

S-Line Fire Pillow are a fire resistant penetration sealing

system used to create a temporary or permanent fire barrier

around single or multi-service penetrations to prevent the

passage of fire through a compartment wall or floor,

especially suitable where services are continuously being

changed or replaced.

General information

Color

Grey

Material

Glass Fibre

Intumescent

Fabric

Guidance for specification option:

Cloth.

Shape

Rectangle

Uniclass

Pr_25_80_81_43 Intumescent pillowsPrimary

CAWS

P12/345 Intumescent pillows

SKU Code

S100FP, S250FP, S800FP

Product range

Others

Specification data - Intumescent pillows

Composition

Glass cloth bag with organic fillers and intumescent additives.

Size

330 x 50 x 20 mm.

Fire performance

To BS EN 1366-3:2009, BS 476 : Parts 20 and 22 and BS EN 13501-2:2016.

Guidance for specification option:

See UL-EU-00640-CPR for fire resistance performance.

For BS 476: Parts 20 and 22, contact technical.fsi.uk@etexgroup.com for details.

Sound insulation rating

To EN 10140, 43 dB.

Air leakage

To EN 1026, 600 Pa.

Guidance for specification option:

Contact technical.fsi.uk@etexgroup.com for details.

Third-party certification

CE Mark ETA-20/1031, UL-EU-00640-CPR; ISO 9001: 11378.

Weight

50g.

Walls

-

Manufacturer guidance

The installer must ensure that all services are within the scope of application for S-Line Pillows as outlined

in UL-EU-00640-CPR. Install the S-Line Fire Pillows in such a way that all joints are staggered in each layer

until you have filled all gaps within the wall or floor.


Walls - S-Line Pillows must be installed centrally within the fire line so as they overlap both sides of the

wall.

Floor surface

-

Manufacturer guidance

The installer must ensure that all services are within the scope of application for S-Line Pillows as outlined

in UL-EU-00640-CPR. Install the S-Line Fire Pillows in such a way that all joints are staggered in each layer

until you have filled all gaps within the wall or floor.


Steel mesh (50 mm square with 5 mm wire) is mechanically fixed with suitable non-combustible fixings to the soffit of the floor or within the reveal of the aperture via vertical returns at the edges of the mesh. The S Line pillows are tightly packed into the opening and around the services.

Sustainability data

Country of product manufacture

United Kingdom

Manufacturing plant location

Material

Glass Fibre
Intumescent
Fabric

Guidance for specification option:

Cloth.

Product certifications

UL-EU Certified

UL-EU-00640-EN - S-Line Pillows