Verified by manufacturer 15 days ago
Design .44 - With actuating mechanism BEN, BEE, BE for 230 V
Hygiene requirements to VDI 6022
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
Certificate of constancy of performance
Certificate type
DoP
Certificate type
EPD
Certificate type
Multi-compartment smoke control damper.
Dampers are designed for using in fire compartments that can be connected to the smoke exhaust ducts (tested according to BS EN 1366-8 or 9) or they can be installed in or on the construction of the fire compartment. The damper can be installed into:
Additional applications may be available, please reference product Technical Specifications for more detail.
Smoke control dampers SEDM-L are designed into an inlet or extract smoke ventilation system. The dampers are designed either to close to provide compartmentation or to open (for fresh air inlet) or to allow removal of the heat and combustible products from a fire in the affected fire zone/ compartment.
The damper blade is controlled by electrical actuating mechanism. Dampers are fire resistant and are intended for systems with manual or automatic activation.
Features and benefits:
Color | White |
Material | Mineral fibre Calcium silicate |
Shape | Square Rectangle |
Length | 250 mm |
Width | 200 mm 250 mm 300 mm 350 mm 400 mm |
Height | 430 mm 630 mm 830 mm 1030 mm 1230 mm |
Uniclass | |
CAWS | U90/445 Dampers, smoke |
Standard | To BS EN 12101-8. |
Classification | |
Standard | To BS EN 13501-4. |
Multi-compartment | |
Integrity class | EI 90.EI 120.Manufacturer guidanceRefer to the manufacturer's literature for placement and installation details to achieve the required fire resistance values. |
High operational temperature | HOT 400/30. |
Suitability | Ve duct.Ve wall.Manufacturer guidanceRefer to the manufacturer's literature for details. |
Smoke leakage | S. |
Under pressures | 1000. |
Inside or outside | (i ↔ o). |
Smoke control use | C modulating. |
Aerodynamic performance | To BS EN 1751.Guidance for specification option: Damper blade tightness: Class 3 (minimum). Damper casing tightness: Class C. |
Activation | MA – manual.AA – automatic. |
Actuators | Belimo BEN, BEE, BE for 230 V. |
Dimensions | Manufacturer guidanceConsult manufacturer's literature for performance details and insert requirements.
|
Control module | Not required. Communication and control module MDCM. Guidance for specification option: The MDCM damper control module is connected on a bi directional communication loop back to a control panel, typically located at the FCC. Communication and control module MDPM. Guidance for specification option: The MDPM damper control module is a combined control module and damper positioning module to provide a balanced/3R position. |
Flanges | Not required. Flange over blades. Flange over damper. Flange and cover grille KMM over blades. Flange and cover grille KMM over damper. Manufacturer guidanceThe surface of the grille is provided with powder coating, standard colour is RAL 9010. Requirements for other colour must be discussed in advance with the manufacturer. |
Material | Mineral fibre Calcium silicate |
Platform | Compatible | Version |
---|---|---|
- | 1 |
Hygiene requirements to VDI 6022
Hygienic assessment - Smoke dampers
UK Conformity Assessed (UKCA)
SEDM-L – Certificate (UKCA)
Certificate of constancy of performance
SEDM-L – Certificate (CE)
DoP
SEDM-L – Declaration of performance (UKCA)
DoP
SEDM-L – Declaration of performance (CE)
EPD
Environmental Product Declaration - Smoke Control Dampers
MSD - EIS AA Multi-Compartment Smoke Control Damper (≤1500x800mm) - Smoke Damper
SEDM - EIS MA Multi-Compartment Smoke Control Damper (≤1600xc1000mm) - Smoke Damper
SEDS - ES AA Single Compartment Smoke Control Damper (≤1600x1000mm) - Smoke Damper
SEDS-L - ES MA Single Compartment Smoke Control Damper (≤1200x1200mm) - Smoke Damper
SEDS-R - ES MA Circular Single compartment smoke control damper (Ø100-630mm) - Smoke Damper