Toughened monolithic (single pane) used to safely contain and guide smoke away from an affected area.
Suitable for internal use, steel bracket smokescreen.
Toughened monolithic pane used to safely contain and guide smoke away from an affected area. Smokeguard products are made to order as they cannot be cut from stock sheets.
Features and benefits:
Color | Clear |
Finish | Glazed |
Material | Glass Guidance for specification option: Monolithic glass. |
Shape | Other Square Rectangle |
Length | 8 mm Guidance for specification option: 400-3600 mm. |
Width | Bespoke Guidance for specification option: 300-2040 mm. |
Height | Bespoke Guidance for specification option: -0.5/+0.5. |
Warranty description | Ten year |
Uniclass | |
CAWS | L20/25 Wood panelled doors H10/115 Patent glazing L40/510 Fire-resistant channel glazing – solid section channel L10/33 Proprietary windows L10/20 Steel windows L10/15 Wood windows L10/10 Wood windows L20/20 Wood flush doors L20/410 Wood doorsets L20/480 Doorsets L10/560 Glazed screen system L10/510 Glazed wood screens L10/480 Roof windows L10/390 Proprietary windows L10/310 Steel windows L10/210 Wood windows L40/65 Fire-resistant tape/ Strip glazing L40/75 Fire-resistant channel glazing – solid section channel L40/515 Fire-resistant channel glazing – plastics/ elastomeric channel L40/80 Fire-resistant channel glazing – plastics/ elastomeric channel L20/280 Doors L20/270 Wood doors L20/45 Doors L20/420 Wood doorsets L20/30 Wood doors H11/110 Curtain walling L20/230 Wood flush doors L20/55 Doorsets L40/505 Fire-resistant tape/ Strip glazing |
Third-party certification | CE UKCA ISO 9001 Classified for performance by Efectis, France. |
Composition | Soda lime silicate.Guidance for specification option: To En 12150-1. |
Thickness | 8 mm.Guidance for specification option: -0.5/+0.5 tolerance. |
Body colour | Clear. |
Performance requirements | |
Fire performance | 30 minutes. |
Light | To EN 410, 90%. |
Impact resistance | To BS EN 12600, 1C1. |
Weight | 20 kg/m². |
TemperatureRange | -100/+100°C. |
Standard | To EN 572, EN 12101-1, EN 12150-2. Guidance for specification option: EN 12101-1 Smoke barriers, EN 12150-2 Toughened safety glass. Manufacturer guidanceProduct standard. |
Size and profile | 2040 x 3600 mm. |
Glass type | Monolithic glass. |
Reaction to fire | To EN 13501-1, A1. |
Sound reduction | To EN 140-3, 32 dB. |
Contains Red List materials | No |
Country of material origin | Europe |
Country of product manufacture | Europe Manufacturer guidanceManufactured in UK and France |