Certificate of constancy of performance
Certificate type
Vertical fire curtain certified to 120 minutes integrity (E) rating, equipped with anti-snag side guide design.
Suited to many different applications; some of the most common are to:
The Adexon FC120E fire curtain is manufactured to prevent the spread of flames and smoke through vertical openings such as doorways, windows, and elevator shafts. In the event of a fire, this curtain automatically deploys, forming a secure barrier that effectively contains fire hazards. The FC120E seamlessly integrates into any architectural style, offering unobtrusive fire safety without compromising aesthetics.
Ideal for commercial, industrial, and residential environments, it can be fully customised to meet specific fire safety standards and design preferences, ensuring both protection and visual harmony
Features and benefits:
Color | Other |
Finish | Galvanized Powder-coated |
Material | Steel Fiber-glass |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke Guidance for specification option: Unlimited. |
Height | Bespoke |
Warranty description | Ten year |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
SKU Code | FC1-E120 |
Standards | Tested and CE marked to BS EN 16034:2014 in conjunction with EN 13241:2003+A2:2016. |
Barrier assemblies | CE marked to BS EN 16034. |
Test standards | Safety and performance to BS EN 16034, fire resistance to BS EN 1634-1 in accordance with BS EN 13501-2. |
Third-party certification | Applus+ Certificate 0370-CPR-6374. |
Size | Guidance for specification option:
|
Performance | |
Durability class | C1. |
Smoke containment | Not required. To BS EN 1634-3:2004. Guidance for specification option: Recommended option. Refer to manufacturer's literature for smoke control curtain sizes. |
Fire resistance | E 120. |
Barrier units | Single. Multiple. |
Deployment | Full. Delayed. Partial deployment. Manufacturer guidanceWith gravity fail safe deployment and controlled decent as standard. |
Activation | Fire alarm signal. Signal from local smoke or heat detector. BMS. |
Accessories | None. Emergency retract buttons. Obstruction warning. Split drop delay. Visual alarm system. Voice alarm system. |
Colour/ Finish | Galvanized. Galvanized and powder-coated. Guidance for specification option: All standard and non-standard PPC colours are available. Insert requirements. |
Headbox | Standard. Side by side. Over and under. |
Bottom bar | Standard bar. Wide/ flat bottom bar. T-bar. |
Contains Red List materials | No |
Material | Steel Fiber-glass |
Recyclability | All components excluding the fire curtain fabric can be recycled. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
Expected Life | Ten year |