NBS Source
I'm a manufacturer

Vertical Fire Curtain - 120 min + Radiation - FC120EW - Fire Curtain

Verified by manufacturer 30 days ago

Adexon Fire & Smoke Curtains Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Vertical fire curtain certified to 120 minutes integrity and radiation rating.

Jump to:
0151 422 9111 Website

Application

Suited to many different applications; some of the most common are to:

  • Compartmentalise open-plan sections in a room or space.
  • Cover exit routes within wide corridors.
  • Cover openings in walls e.g. serving hatches.
  • Cover non-fire-rated doors or glazing.
  • Cover lifts and lift shafts that can act as fire or smoke chutes.
  • Protect escape routes.
  • Provide boundary protection.

Description

A vertically operating fire curtain barrier with in-built integrity (E) and radiation (W) ratings. This limits and controls the spread of fire (e) while also reducing radiation

emission to less than 15 kW/m²·K at a distance of 1 m from the fabric (W), with a maximum classification of 120 minutes.


Features and benefits:

  • The system is tested and certified to BS EN 16034:2014, with smoke control tested to BS EN 1634-3:2004.
  • Operation is via 24 V d.c. tubular motors controlled by an electronic control board.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Steel

Fiber-glass

Polyurethane

Shape

Rectangle

Length

Bespoke

Width

Bespoke

8800 mm

Guidance for specification option:

Maximum.

Height

Bespoke

5500 mm

Guidance for specification option:

Maximum.

Warranty description

Ten year

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

-

Barrier assemblies

CE marked to BS EN 16034.

Test standards

Safety and performance to BS EN 16034, fire resistance to BS EN 1634-1 in accordance with BS EN 13501-2.

Third-party certification

Applus+ Certificate 0370-CPR-6850.

Size

Guidance for specification option:

  • Curtain maximum dimensions: 8.8 x 5.5 m (width x height). Insert requirements or refer to a drawing.
  • Determine project requirements on a curtain-by-curtain basis through detailed design and scheduling. Refer to drawings for locations.

Performance

-

Smoke containment

Not required.

To BS EN 1634-3:2004.

Guidance for specification option:

Recommended option. Refer to manufacturer's literature for smoke control curtain sizes.

Fire resistance

EW 120.

Barrier units

Single.

Multiple.

Activation

Fire alarm signal.

Signal from local smoke or heat detector.

BMS.

Colour/ Finish

Galvanized.

Galvanized and powder-coated.

Guidance for specification option:

All standard and non-standard PPC colours are available. Insert requirements.

Bottom bar

Standard bar.

Wide/ flat bottom bar.

T-bar.

Sustainability data

Contains Red List materials

No

Material

Steel

Fiber-glass

Polyurethane

Recyclability

All components excluding the fire curtain material can be recycled.

Expected Life

Ten year

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

Adexon-FC120EW Verticle Fire Curtain (Integrity & Radiation & Smoke) - Certificate 0370-CPR-6850 -- EN 16034_2014 -- Exp 25,06,30

Literature

FC120EW Uniclass Spec

FC120EW Uniclass Spec

FC120EW Drawing

FC120EW Drawing