Certificate type
"BS EN 1366-10 AA certified" smoke control damper, with a fire resistance (EIS) upto 120 minutes. For installation in walls (fire compartment boundaries).
"BS EN 1366-10 AA certified" smoke control damper, with a fire resistance (EIS) upto 120 minutes.
For installation in walls (fire compartment boundaries).
VUW120 Fields of application:
VUW120 building applications:
"BS EN 1366-10 AA certified" smoke control damper, with a fire resistance (EIS) upto 120 minutes.
For installation in walls (fire compartment boundaries).
VUW120 Distinct Product Features
VUW120 User Benefits:
VU120 Range: (Width/Height)
Notes:
Color | Silver Cream |
Finish | Other Galvanized |
Material | Calcium silicate Metal Steel |
Shape | Rectangle Square |
Length | 400 mm Guidance for specification option: Depth. |
Width | 300 mm 350 mm 400 mm 450 mm 500 mm Manufacturer guidanceNominal. |
Height | 300 mm 350 mm 400 mm 450 mm 500 mm Manufacturer guidanceNominal. |
Warranty description | One year |
Uniclass | |
CAWS | U90/445 Dampers, smoke |
Standard | To EN 12101-8:2011. |
Classification | |
Standard | To EN 13501-4. |
Multi-compartment | |
Integrity class | EI 120. |
High operational temperature | NPD. |
Suitability | Ve wall. |
Smoke leakage | S. |
Under pressures | 1500. |
Inside or outside | (i ↔ o). |
Smoke control use | C10000. |
Aerodynamic performance | To EN 1751, air tightness class B.To EN 1751, air tightness class C. |
Activation | AA – automatic. |
Actuators | KITS BLE24.Guidance for specification option: BLE 24 V actuator for smoke control dampers. KITS BLE24-ST.Guidance for specification option: BLE 24 V actuator for smoke control dampers with plug (ST). KITS BLE230.Guidance for specification option: BLE 230 V actuator for smoke control dampers. |
Dimensions | Guidance for specification option: Consult manufacturer's literature for performance details and insert requirements:
Overall height = nominal height + 24 mm. Overall width = nominal width + 24 mm. Intermediate dimensions available on request; consult manufacturer for details. Consult manufacturer for performance data and unit weights based on requirements (18.8–116.7 kg). |
Accessories | MECT testbox for mechanisms 24/ 48 V. UL inspection shutters. EQ equipotential connection. BOX thermal protection housing. |
Third-party certification | CE marked Efectis_1812_CPR_1596. |
Integral accessories | PG30 flange. Guidance for specification option: Connection to ducts with 30 mm flanges (either by sliding profile, or with bolts, or with clamps). Elliptical holes Ø 8.5 x 16 mm. |
Country of material origin | Belgium |
Country of product manufacture | Slovakia |
AVANTAGE MP - Multi Purpose SCD with Grille - Motorized Smoke Control Shutter
KAMOUFLAGE AP - All Purpose, Architectural SCD - Smoke Control Damper
KAMOUFLAGE MP - Multi Purpose, Architectural SCD - Smoke Control Damper
Markage MB - Smoke Control Damper - Multi-blade - Rectangular Smoke Control Damper
VU120 - Smoke Control Damper - Single-blade - Rectangular Smoke Control Damper