Fire Curtain - Vertical Flameshield 8524 Overlapping Fire Curtain - Fire Curtain

Verified by manufacturer 1 day ago

8524 - No Smoke Seals

A1S Group Variant:

An automatic vertical overlapping fire curtain barrier that has 120 minutes integrity and 74 minutes radiation, tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.

Jump to:
+44 (0)1204 383839 Website

Application

The Flameshield 8524 Overlapping Fire Curtain is designed for multiple applications such:

  • Protected means of escape
  • Atrium
  • Lobbies
  • Receptions
  • Openings in walls
  • Egress
  • Corridor separation
  • Boundary protection
  • Escalators
  • Stairs
  • Lifts and lift lobbies
  • Hospitals
  • Schools
  • Hotels
  • High Buildings
  • Offices
  • Military sites
  • Retail
  • Stadia
  • Museums and galleries
  • Prisons
  • Train stations
  • Airports
  • Warehouses
  • Factories
  • Nurseries
  • Shopping centres
  • Restaurants

Description

The automatic vertical overlapping fire curtain is comprised of a carbon steel barrel and motor incorporating an attached fabric curtain. The barrel deflection conforms to the necessary British Standard BS 6323-5, the fabric can withstand temperatures in excess of 1000°C and the two section bottom rail allows smooth operation of the curtain. The fire barrier shall be powered by an internal 24 V d.c electric motor that has all of the applicable safety standards.

Fully compliance-tested and include fail-safe features enabling them to operate even if there’s a power failure. 

The Flameshield 8524 Overlapping Fire Curtain is an excellent product if aesthetics of the building need to be maintained. The fire curtain's end plates, guides and head boxes can be finished with specialist RAL colours.

Egress switches, access switches, obstruction warnings, and heat and smoke alarms are fully tested to the ancillary equipment Annex H as stipulated by BS 8524-1.

Features and benefits:

  • Gravity fail safe closes without mains power.
  • Provides smoke control.
  • Lightweight slimline compact design.
  • Two stage closing operation.
  • Compliance tested to maintain building fire safety and integrity in accordance with BS 8524-1 and installed in accordance with BS 8524-2.
  • Can be hidden neatly above the ceiling line to assist the building design and aesthetics.
  • Voice warning devices available.
  • Fully resets after fire test without the need for engineers to attend.
  • Low maintenance costs.
  • Timed delay closing.

All fire curtains are tested and approved by Warrington Fire Research Centre and Exova. The curtains constructed to Warrington Fire Research Centre, the tests in accordance with BS EN 1634-1 for fire and radiation (radiation and tenability replaces the insulation zone) in accordance with BS 8524. The construction and manufacture is in accordance with Warrington test WF 366190. Manufactured in accordance with certain sections of the new European Standard BS EN 16034.

General information

Color

Other

Finish

Powder-coated

Material

Carbon steel

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

To BS 8524-1, BS EN 1634-1, BS 476-6 and -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034.

Barrier assemblies

To BS 8524-1.

Test standards

Vertical, horizontal and angled to BS EN 1634-1.

Third-party certification

Warrington Fire Report 367279.

Size

-

Manufacturer guidance

Maximum size (w x h): 8000 x 8000 mm. (32 m²). Insert requirements.

Performance

-

Smoke containment

No Smoke Seals.

Fire resistance

60 minutes.
120 minutes.

Accessories

Partial Drop.

Guidance for specification option:

The barrier shall have the facility to deploy to a pre-determined position to allow escape and initial smoke containment. The partial close position shall be site adjustable with an adjustable wait time in the partial close position of up to 10 minutes

Emergency Retract.

Guidance for specification option:

The barrier can have an emergency retract interface for escape and emergency access. The interface shall be volt free, normally open (close on operation). The signal required shall be momentary with a site adjustable retract time. The emergency retract facility shall be operational as long as there is primary / secondary power available.

BMS Interface.

Guidance for specification option:

The barrier has volt free c/o contacts to indicate whether the barrier is fully open or fully closed.

Obstruction Beam Detection Device.

Guidance for specification option:

An obstruction beam detection device, with on site adjustable time module between 5 minutes and 10 minutes, shall sound in the event of an obstruction being present as along as mains power is available. The obstruction device shall not stop the barrier from deploying it to its active position. Where sensory equipment for detecting obstructions to barrier assemblies is provided they shall conform with BS 8524-1 (5.8.5).

Audio / Visual / Spoken Warning Unit.

Guidance for specification option:

The barrier has a volt free contact which indicates an active c/o (change over) contact which indicates an active alarm signal. An Audio / Visual / Spoken warning unit can be interfaced with this using power supplied by the primary / secondary source or via an external source.

Radiation

74 minutes at 15 kW/m².

Fabric

Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.

Barrel

Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.

Sustainability data

Material

Carbon steel

Literature

A1S Flameshield Overlapping Fire Curtain 8524 Specification

A1S Flameshield Overlapping Fire Curtain 8524 Specification

A1S Flameshield Overlapping Fire Curtain 1634 Specification

A1S Flameshield Overlapping Fire Curtain 1634 Specification

Similar products from A1S Group

Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain

Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain

Fire Curtain - Vertical Flameshield EVO Fire and Smoke Curtain - Fire and Smoke Curtain

Fire Curtain - Vertical Flameshield EVO Fire and Smoke Curtain - Fire and Smoke Curtain

Fire Curtain - Vertical Flameshield EW120 Fire and Smoke Curtain - Fire Curtain

Fire Curtain - Vertical Flameshield EW120 Fire and Smoke Curtain - Fire Curtain