NBS Source
I'm a manufacturer

Firestrip® 60

Verified by manufacturer 3 months ago

Hodgson Sealants

An intumescent strip sealant which can provide 60 minutes resistance to the passage of fire when used to glaze fire rated glass into internal timber doors and softwood or hardwood timber screens.

Jump to:
+44 (0)1482 868321 Website

Application

  • The product is used for glazing semi-insulating and insulating glass into timber fire doors or hardwood timber screens with hardwood beads.
  • Consult literature for details of which glass can be glazed using Firestrip® 60.
  • Dependent on the use of suitable fire resistant glass and suitable frame design. Consult the manufacturer for further details.

Description

An intumescent strip sealant which can provide 60 minutes resistance to the passage of fire when used to glaze fire rated glass into internal doors and timber screens.


Features and benefits:

  • Fully tested to provide 60 minutes resistance to the passage of fire and smoke in timber doors and screens.
  • British Woodworking Federation (BWF) Certifire Scheme Certificate No. CF297 for use in timber screens and doors for periods of 60 minutes fire resistance.
  • Suitable for use by FIRAS Accredited Glaziers.
  • High tack surface provides good adhesion.
  • Tested with semi-insulating and fully insulating glasses to give 60:0 and 60:60 (Integrity: Insulation) respectively.
  • Can be over-coated with paints and decorative wood stains.
  • Cost-effective compared to other rigid/ semi-rigid fire-resistant materials.
  • Non-toxic.
  • High resistance to mould.
  • No slump or staining.
  • Very good tack.


Standards/ Approvals:

  • EN 1364-1 and EN 1634-4.
  • Glass and Glazing Federation Glazing Manual Section 2.8 Fire Resistant.
  • Glazing, 13. Table of Tested Products and Materials. 9.1.2 Glazing Materials – Strips.
  • FIRAS register of specialist fire protection materials – Manufacturers and Suppliers.

General information

Color

White

Guidance for specification option:

Off-white.

Other

Guidance for specification option:

Mahogany.

Uniclass

Pr_25_80_81_29 Flexible intumescent gap sealsPrimary

CAWS

P12/330 Flexible intumescent gap sealer

Product range

Fire Rated Range

Specification data - Flexible intumescent gap seals

Size

12 mm x 15 m.

Manufacturer guidance

Width x length.

Fire performance

Fully tested to provide 60 minutes resistance to the passage of fire and smoke.

Colour

Mahogany.

Off-white.

Thickness

3 mm.

Adhesion

Excellent (to glass and timber).

Compression component

Compression to seal: Positive compression; Force to compress by 20%: 1.4 kg/cm².

Density

1.2 g/cm³.

Movement

±10% (accommodation).

TensileStrength

1.3 kg/cm².

UV resistance

Excellent.

Application temperature range

+5 to +30°C.

Service temperature range

+5 to +40°C.

Standards

To EN 1364-1 and EN 1634-4.

Third-party certification

FIRAS.

Literature

Firestrip 60

Firestrip 60