NBS Source
I'm a manufacturer

WIP Pro V Damper - Smoke Damper

Verified by manufacturer 4 days ago

Mercor Fire Protection UK LTD

Multi-blade smoke control dampers for multi-compartment fire ventilation systems.

Jump to:
Website

Application

  • For installation in automatically operated fire ventilation systems.
  • Dampers may be installed in smoke extract ducts, shafts and at system ends.
  • Suitable for production halls and warehouses, logistics centres, public buildings, commercial buildings and residential buildings.

Description

Multi-blade smoke control dampers for multi-compartment fire ventilation systems.

mcr WIP PRO/V cut-off dampers are designed for installation in automatically-activated fire ventilation systems. They support single fire zones, as well as several zones within a single facility. They prevent propagation of fire, smoke and fire gases to the neighbouring zones.

Features and benefits:

  • Small thickness of damper - 135 mm.
  • Cut-off barrier does not protrude outside the damper body, regardless of damper dimensions.
  • Possible installation in a partition, on a duct ended with a duct cover.
  • Option of making dampers with penetrations for rounded ducts.

General information

Color

Cream

Finish

Galvanized

Material

Steel

Stainless steel

Shape

Rectangle

Width

110 mm

150 mm

200 mm

250 mm

300 mm

Show more

Height

270 mm

300 mm

350 mm

390 mm

450 mm

Show more

Uniclass

Pr_65_65_24_80 Smoke dampersPrimary

CAWS

U90/445 Dampers, smoke

Specification data - Smoke dampers

Classification data

Standard

To EN 12101-8.

Classification

-

Standard

To EN 13501-4.

Multi-compartment

-

Integrity class

EI 120.

Suitability

Ve wall/ Ve duct/ Ho duct.

Smoke leakage

S.

Under pressures

1000.

Inside or outside

(i ↔ o).

Smoke control use

C10 000.

Actuators

Belimo BE24.

Guidance for specification option:

Actuator without a return spring, U = 24 V a.c./d.c.

Belimo BE24-ST.

Guidance for specification option:

With BKE230-24 option – actuator without a return spring, for the SBS control system.

Belimo BE230.

Guidance for specification option:

Actuator without a return spring, U = 230 V a.c./d.c.

Belimo BEE24.

Guidance for specification option:

Actuator without a return spring, U = 24 V a.c./d.c.

Belimo BEE24-ST.

Guidance for specification option:

With BKE230-24 option – actuator without a return spring, for the SBS control system.

Belimo BEE230.

Guidance for specification option:

Actuator without a return spring, U = 230 V a.c./d.c.

Belimo BEN24.

Guidance for specification option:

Actuator without a return spring, U = 24 V a.c./d.c.

Belimo BEN24-ST.

Guidance for specification option:

With BKE230-24 option – actuator without a return spring, for the SBS control system.

Belimo BEN230.

Guidance for specification option:

Actuator without a return spring, U = 230 V a.c./d.c.

Material

Galvanized steel.

Guidance for specification option:

Zn 275 g/m² coating.

Stainless steel.
1.4404 acid-proof steel.

Rotation

Horizontal axis.
Vertical axis - mechanism at the bottom of the damper.
Vertical axis - mechanism at the top of the damper.

Accessories

Not required.
mcr KRP connection stub.

Guidance for specification option:

To connect a circular ventilation duct to a rectangular damper.

Design

Left damper.
Right damper.
Actuator long casing.

Sustainability data

Material

Steel
Stainless steel

Literature

mcr WIP PRO V

mcr WIP PRO V

Similar products from Mercor Fire Protection UK LTD

FID SV Damper - Fire Dampers

FID SV Damper - Fire Dampers

WIP LD Damper - Smoke Damper

WIP LD Damper - Smoke Damper