Verified by manufacturer 4 days ago
Multi-blade smoke control dampers for multi-compartment fire ventilation systems.
Multi-blade smoke control dampers for multi-compartment fire ventilation systems.
mcr WIP PRO/V cut-off dampers are designed for installation in automatically-activated fire ventilation systems. They support single fire zones, as well as several zones within a single facility. They prevent propagation of fire, smoke and fire gases to the neighbouring zones.
Features and benefits:
Color | Cream |
Finish | Galvanized |
Material | Steel Stainless steel |
Shape | Rectangle |
Width | 110 mm 150 mm 200 mm 250 mm 300 mm |
Height | 270 mm 300 mm 350 mm 390 mm 450 mm |
Uniclass | |
CAWS | U90/445 Dampers, smoke |
Classification data | |
Standard | To EN 12101-8. |
Classification | |
Standard | To EN 13501-4. |
Multi-compartment | |
Integrity class | EI 120. |
Suitability | Ve wall/ Ve duct/ Ho duct. |
Smoke leakage | S. |
Under pressures | 1000. |
Inside or outside | (i ↔ o). |
Smoke control use | C10 000. |
Actuators | Belimo BE24. Guidance for specification option: Actuator without a return spring, U = 24 V a.c./d.c. Belimo BE24-ST. Guidance for specification option: With BKE230-24 option – actuator without a return spring, for the SBS control system. Belimo BE230. Guidance for specification option: Actuator without a return spring, U = 230 V a.c./d.c. Belimo BEE24. Guidance for specification option: Actuator without a return spring, U = 24 V a.c./d.c. Belimo BEE24-ST. Guidance for specification option: With BKE230-24 option – actuator without a return spring, for the SBS control system. Belimo BEE230. Guidance for specification option: Actuator without a return spring, U = 230 V a.c./d.c. Belimo BEN24. Guidance for specification option: Actuator without a return spring, U = 24 V a.c./d.c. Belimo BEN24-ST. Guidance for specification option: With BKE230-24 option – actuator without a return spring, for the SBS control system. Belimo BEN230. Guidance for specification option: Actuator without a return spring, U = 230 V a.c./d.c. |
Material | Galvanized steel. Guidance for specification option: Zn 275 g/m² coating. Stainless steel. 1.4404 acid-proof steel. |
Rotation | Horizontal axis. Vertical axis - mechanism at the bottom of the damper. Vertical axis - mechanism at the top of the damper. |
Accessories | Not required. mcr KRP connection stub. Guidance for specification option: To connect a circular ventilation duct to a rectangular damper. |
Design | Left damper. Right damper. Actuator long casing. |